RA3.8.1 Purpose and Scope

p.4362025 Residential Appendices of the directory ratings at 32 degrees Fahrenheit shall not be allowed.

Equation on PDF page 436: Equation RA3.7-2 sre = sre1 + [(na – na1) / (na2 – na1)] X (sre2 – sre1)

Equation text: Equation RA3.7-2 sre = sre1 + [(na – na1) / (na2 – na1)] X (sre2 – sre1)

Needs visual review

p.436

p.436where:

p.436na is the known value for Net Airflow equal to the ventilation airflow required on the

p.436certificate of compliance.

p.436sre is the unknown value for SRE at 32 degrees Fahrenheit.

p.436na1 and sre1 are the closest rated values at 32 degrees Fahrenheit for Net Airflow

p.436(cfm) and SRE respectively that are below the known na value.

p.436na2 and sre2 are the closest rated values at 32 degrees Fahrenheit for Net Airflow

p.436(cfm) and SRE respectively that are above the known na value.

p.4365. Determining Compliance.

p.436a. If the value determined for SRE by one or both of the alternatives in step 4 for the

p.436installed system is greater than or equal to the SRE required for compliance, then the system complies with the sensible recovery efficiency rating requirement. Otherwise the system does not comply.

p.436b. If the value determined for fan efficacy (W/cfm) by one or both of the alternatives in step

p.4363 for the installed system is less than or equal to the fan efficacy required for compliance, then the system complies with the fan efficacy rating requirement. Otherwise, the system does not comply.

p.436c. If compliance with both fan efficacy and sensible recovery efficiency ratings are required,

p.436then both ratings shall comply at the same Net Airflow (cfm), otherwise the system does not comply.

p.436d. If the system is not listed in the HVI or other CEC-approved directory, then the system

p.436does not comply.

p.436RA3.8 Field Verification and Diagnostic Testing of Air Leakage of Building

p.436Enclosures and Dwelling Unit Enclosures

p.436RA3.8.1 Purpose and Scope

p.436The purpose of this test procedure is to measure the air leakage rate through a building enclosure or a dwelling unit enclosure.

p.436The measurement procedure shall be based on the specifications of Residential Energy Services Network's (RESNET) Standard for Testing Airtightness of Building, Dwelling Unit, and Sleeping Unit Enclosures; Airtightness of Heating and Cooling Air Distribution Systems; and Airflow of Mechanical Ventilation Systems (ANSI/RESNET/ICC 380-2019) (RESNET 380) as further specified in Subsections RA3.8.2, RA3.8.3, RA3.8.4 below.

p.436This enclosure leakage procedure is applicable to:

p.436– Residential Field Verification and Diagnostic Test Protocols