RA3.7.4.3 Kitchen Local Mechanical Exhaust - Vented Range Hood Verification

p.4342025 Residential Appendices provide at least the minimum ventilation airflow required by the Standards, and subject to consideration of the manufacturer's proposed field verification and diagnostic test protocol for the ventilation system(s). Ventilation airflow of systems with multiple operating modes shall be tested in all modes designed to comply with the required ventilation airflows.

p.4352025 Residential Appendices ratings in the HVI, or other CEC-approved directory in accordance with steps a, b, and c below.

p.435a. Record the required ventilation airflow (cfm) for the installed HRV/ERV as specified on the

p.435certificate of compliance.

p.434Approved systems, devices, or controls, and field verification and diagnostic test protocols for intermittent mechanical ventilation systems shall be listed in directories published by the Energy Commission.

p.435b. From the energy ratings in the HVI or other CEC approved directory, determine, and

p.435record the rated Power Consumed (Watts) at 32 degrees Fahrenheit, at the closest Net Airflow (cfm) listed in the directory that is greater than or equal to the ventilation airflow (cfm) required on the certificate of compliance. Alternatively, linear interpolation of the directory ratings at 32 degrees Fahrenheit shall be allowed if the interpolated value is calculated based on a Net Airflow (cfm) that is equal to the ventilation airflow (cfm) required on the certificate of compliance. Interpolation shall be in accordance with equation RA3.7-1. Extrapolation of the directory ratings at 32 degrees Fahrenheit shall not be allowed.

p.434RA3.7.4.3 Kitchen Local Mechanical Exhaust - Vented Range Hood Verification

p.434The verification shall utilize certified performance rating data from the Home Ventilating Institute (HVI) Certified Home Ventilating Products Directory at https://www.hvi.org/hvi-certified­ products-directory/ the Association of Home Appliance Manufacturers (AHAM) Certified Products Directory at https://www.aham.org/AHAM/What_We_Do/Kitchen_Range_Hood_Certification, or another directory of certified product performance ratings approved by the Energy Commission for determining compliance. The verification procedure shall consist of visual inspection of the installed kitchen range hood to verify and record the following information:

Equation on PDF page 435: Equation RA3.7-1 pc = pc1 + [(na – na1) / (na2 – na1)] X (pc2 – pc1)

Equation text: Equation RA3.7-1 pc = pc1 + [(na – na1) / (na2 – na1)] X (pc2 – pc1)

Needs visual review

p.435

p.435where:

p.434(a) The manufacturer name and model number.

p.435na is the known value for Net Airflow equal to the ventilation airflow required on the

p.434(b) The model is listed in the HVI, AHAM, or other CEC-approved directory.

p.435certificate of compliance.

p.434(c) The rated airflow value or rated capture efficiency value listed in the HVI, AHAM, or other

p.435pc is the unknown value for Power Consumed (Watts) at 32 degrees Fahrenheit.

p.434CEC-approved directory.

p.435na1 and pc1 are the closest rated values at 32 degrees Fahrenheit for Net Airflow

p.434(d) The sound rating value listed in the HVI, AHAM, or other CEC-approved directory.

p.435(cfm) and Power Consumed (Watts) respectively that are below the known na value.

p.434(e) If the value for the rated airflow or rated capture efficiency given in the directory is

p.434greater than or equal to the airflow or capture efficiency requirements specified in the Standards, and if the value for the sone rating given in the directory is less than or equal to the sone rating requirements specified in Standards, then the kitchen range hood complies. Otherwise, the kitchen range hood does not comply. If the kitchen range hood is not listed in the HVI, AHAM, or other CEC-approved directory, then the system does not comply.

p.435na2 and pc2 are the closest rated values at 32 degrees Fahrenheit for Net Airflow

p.435(cfm) and Power Consumed (Watts) respectively that are above the known na value.

p.435c. Divide the value for Power Consumed (Watts) recorded in step b, by the Net Airflow (cfm)

p.435used in step b to determine the Power Consumed.

p.4354. If compliance with a sensible recovery efficiency (SRE) performance rating (%) is required, then determine and record the SRE rating for the installed model using the model details in the energy ratings in the HVI or other CEC-approved directory in accordance with steps a, and b below.

p.434RA3.7.4.4 Heat Recovery Ventilation (HRV) or Energy Recovery Ventilation (ERV) Rated Performance Verification

p.434The verification shall utilize certified performance rating data from the Home Ventilating Institute (HVI) Certified Home Ventilating Products Directory at https://www.hvi.org/hvi-certified­ products-directory/ or another directory of certified product performance ratings approved by the Energy Commission for determining compliance. The verification procedure shall consist of visual inspection of the installed system to verify and record the following information:

p.435a. Record the required ventilation airflow (cfm) for the installed HRV/ERV as specified on the

p.435certificate of compliance.

p.435b. From the energy ratings in the HVI or other CEC approved directory, determine, and

p.435record the rated SRE (%) at 32 degrees Fahrenheit, at the closest Net Airflow (cfm) listed in the directory that is greater than or equal to the ventilation airflow (cfm) required on the certificate of compliance. Alternatively, linear interpolation of the directory ratings at 32 degrees Fahrenheit shall be allowed if the interpolated value is calculated based on a Net Airflow (cfm) that is equal to the ventilation airflow (cfm) required on the certificate

p.4341. Record the manufacturer make and model from the installed system nameplate.

p.4342. Verify the model is listed in the HVI or other CEC-approved directory.

p.4343. If compliance with a fan efficacy performance rating (w/cfm) is required, then determine and record the fan efficacy rating for the installed model using the model details in the energy

p.434– Residential Field Verification and Diagnostic Test Protocolsp.435

p.435Appendix RA3– Residential Field Verification and Diagnostic Test Protocols