RA3.2.1 Purpose and Scope

p.3382025 Residential Appendices clean-filter pressure drop at the design airflow rate posted on a label/sticker, inside or near the location of the filter grille/rack such that this information will be visible to a person replacing the air filter.

p.338Field inspection shall verify that each air filter installation location has the required sticker. If the air filter installation location does not have the required sticker, the indoor unit does not comply.

p.338(d) Air filter manufacturer's performance rating label. Standards section 150.0(m)12E

p.338requires that the air filter placed in the filter grille/rack shall be labeled by the air filter manufacturer to disclose the clean filter pressure drop performance determined according to ASHRAE Standard 52.2 or AHRI Standard 680. The required air filter label information includes clean filter pressure drop ratings at a range of airflow rates.

p.338Field inspection shall verify that the air filter installed in the filter grille/rack has the required performance rating label. If an installed air filter does not have the required manufacturer's performance rating label, then the indoor unit does not comply.

p.338(e) Determining clean filter pressure drop compliance. Inspection of the air filter

p.338manufacturer's performance rating label shall verify that the air filter is rated to provide a clean filter pressure drop less than or equal to the value required for compliance, at an airflow rate greater than or equal to the design airflow for the filter. Interpolation of the manufacturer's airflow and pressure drop rating values published on the air filter performance rating label is allowed when determining compliance. Field diagnostic pressure measurements of operating indoor units to determine the pressure drop of installed air filters are not required for demonstrating compliance.

p.338If all of the indoor unit air filters are rated to operate at a pressure drop less than or equal to the value required for compliance, and at an airflow rate greater than or equal to the design airflow for the air filter, then the indoor unit complies.

p.338RA3.2 Field Verification and Diagnostic Testing of Refrigerant Charge for Air Conditioners and Heat Pumps

p.338RA3.2.1 Purpose and Scope

p.338(a) The procedures in Appendix RA3.2 are for use for residential air-cooled air conditioners

p.338and air-source heat pumps to verify the systems have the required refrigerant charge.

p.338(b) For dwelling units with multiple air conditioners or heat pumps, the procedures shall be

p.338applied to each system separately.

p.338(c) Appendix RA3.2 defines two procedures, the Standard Charge Verification Procedure in

p.338Section RA3.2.2 and the Weigh-in Charging procedure in Section RA3.2.3.

p.338(d) Sections 150.1(c)7 and 150.2(b)1F specify the requirements for minimum system airflow

p.338rates to be verified in conjunction with the refrigerant charge verification.

p.338Appendix RA3– Residential Field Verification and Diagnostic Test Protocols