p.3392025 Residential Appendices (e) Failure to follow the manufacturer’s installation and charging instructions may result in
p.339significant refrigeration system faults that may invalidate refrigerant charge and metering device verification results. The installer shall certify that he/she has conformed to the manufacturer’s instructions and specifications for charging the system prior to proceeding with the verification procedures in this appendix.
p.339(f) In the case where the Energy Commission has approved an alternative protocol as
p.339described in RA1, the HVAC Installer and ECC-Rater may choose to perform the alternative refrigerant charge verification procedure.
p.339RA3.2.1.1 Scope of the Standard Charge Verification Procedure (RA3.2.2)
p.339(a) The procedures in Section RA3.2.2 are applicable to ducted split system air-cooled air
p.339conditioners and ducted split system air-source heat pumps, and may be applicable to packaged air-cooled air conditioners and packaged air-source heat pumps.
p.339(b) The procedures in Section RA3.2.2 require verification of the applicable minimum system
p.339airflow rate across the cooling coil when refrigerant charge is verified.
p.339(c) The procedures in Section RA3.2.2 require verification (for applicable systems) that the
p.339metering device is operating properly.
p.339(d) The procedures in Section RA3.2.2 may be used when the outdoor air temperature is 55°F
p.339or above.
p.339(e) When refrigerant charge verification is required for compliance, the applicable
p.339procedures in Section RA3.2.2 shall be used by the HVAC installer after installing a new HVAC system or after altering refrigerant-containing components in an existing HVAC system, and after charging the air conditioner or heat pump system in accordance with the manufacturer's instructions and specifications.
p.339(f) The applicable procedures in Section RA3.2.2 shall always be used by the ECC-Rater for
p.339verification of the system's refrigerant charge when verification is required for compliance unless an applicable alternate procedure is available in Reference Residential Appendix RA1, or the Standards specify the Section RA3.2.3.2 procedure (observation of weigh-in) as mandatory for compliance, or as an available option for compliance and the HVAC installer elects to use the RA3.2.3.2 procedure for verification.
p.339(g) When the procedures in Section RA3.3.3.1.5 (alternative to compliance with minimum
p.339system airflow) are utilized for compliance, verification compliance shall not use group sampling.
p.339RA3.2.1.2 Scope of the Weigh-In Charging Procedure (RA3.2.3)
p.339(a) The procedures in Section RA3.2.3 are applicable to air-cooled air conditioners or air-
p.339source heat pumps.
p.339(b) The weigh-in charging procedure is an acceptable method for demonstrating compliance
p.339at any outdoor temperature.
p.339(c) Use of the Section RA3.2.3 procedure does not change the obligation for the system to
p.339comply with all applicable minimum airflow rate verification requirements.
p.339Appendix RA3– Residential Field Verification and Diagnostic Test Protocols