RA3.2.2 Standard Charge Verification Procedure

p.3402025 Residential Appendices (d) When the procedures in Section RA3.2.3 are utilized by the HVAC installer, verification

p.3412025 Residential Appendices

TableRA3.2-1 – Refrigerant ChargeVerification Protocols and Compliance Criteria
CaseUser ApplicationCompliance CriteriaProcedure(s)
Standard Charge Verification Procedure - Fixed Metering Device SystemsInstaller Testing at Final55°F ≤ Outdoor Air Dry-bulb Temp ≤ 115°F Return Air Dry-bulb Temp ≥ 70°F Return Air Wet-bulb Temp ≤ 76°F Superheat tolerance ±5°F of the specified targetRA3.2.2.6.1
Standard Charge Verification Procedure - Fixed Metering Device SystemsECC-Rater Testing55°F ≤ Outdoor Air Dry-bulb Temp ≤ 115°F Return Air Dry-bulb Temp ≥ 70°F Return Air Wet-bulb Temp ≤ 76°F Superheat tolerance ±8°F of the specified targetRA3.2.2.6.1
Standard Charge Verification Procedure - Variable Metering Device SystemsInstaller Testing at Final55°F ≤ Outdoor Air Dry-bulb Temp ≤ 120°F Return Air Dry-bulb Temp ≥ 70°F Subcooling tolerance ±3°F of the manufacturer-specified target1 Metering Device tolerance: Superheat meets the Manufacturer's specifications or 4°F ≤ Superheat ≤ 25°FRA3.2.2.6.2
Standard Charge Verification Procedure - Variable Metering Device SystemsECC-Rater Testing55°F ≤ Outdoor Air Dry-bulb Temp ≤ 120°F Return Air Dry-bulb Temp ≥ 70°F Subcooling tolerance ±6°F of the manufacturer-specified target1 and Subcooling ≥2°F Metering Device tolerance: Superheat meets the Manufacturer's specifications or 3°F ≤ Superheat ≤ 26°FRA3.2.2.6.2
Note: 1. If a manufacturer-specified subcooling compliance.target value is not available orcannot be determined, the Executive Director may provide additionalguidance for

p.340compliance shall not use group sampling.

p.340(e) The procedures in Section RA3.2.3.1 may be used by the HVAC installer as an alternative

p.340to the Standard Charge Verification Procedure in RA3.2.2, or as an alternative to any applicable Alternative Refrigerant Charge Verification Protocol in Reference Residential Appendix RA1.

p.340(f) The procedures in Section RA3.2.3.1 shall be used by HVAC installers when refrigerant

p.340charge verification is required for compliance when the outdoor air temperature is below 55°F, and there is no applicable alternative refrigerant charge verification protocol in Reference Residential Appendix RA1 available for use with the system for outdoor temperatures below 55°F.

p.340(g) The procedures in Section RA3.2.3.1 shall be used by HVAC installers when refrigerant

p.340charge verification is required for compliance when the standard charge verification procedure in RA3.2.2 is not applicable to the system that must demonstrate compliance, and there is no applicable alternative refrigerant charge verification protocol in Reference Residential Appendix RA1 available for use with the system.

p.340(h) The procedures in Section RA3.2.3.1 shall not be utilized by ECC-Raters for verification of

p.340(i) The procedures in Section RA3.2.3.2 shall be utilized by ECC-Raters for verification of

p.340refrigerant charge only when the Standards specify that the RA3.2.3.2 procedure shall be used for verification compliance, otherwise only when the Standards specify the RA3.2.3.2 procedure is an available option, and the HVAC installer elects to use the RA3.2.3.2

p.340This section specifies the standard charge verification procedure. Under this procedure, the refrigerant charge is verified using the "superheat charging method" for systems with fixed metering devices, or the "subcooling charging method" for systems with thermostatic expansion valves (TXV) or electronic expansion valves (EXV).

p.340The following sections describe the required instrumentation; required calibration for the instrumentation; required diagnostic measurements; and the required calculations to determine results that must be compared to the criteria in Table RA3.2-1 to determine compliance.

p.341Appendix RA3– Residential Field Verification and Diagnostic Test Protocols

p.340Refrigerant charge verification utilizing the procedures in Section RA3.2.2 requires compliance with a minimum airflow rate across the cooling coil at the time of charge verification, as specified by Standards Sections 150.1(c)7Aib and 150.2(b)1Fiia as applicable.

p.340Table RA3.2-1 summarizes the standard charge verification protocols and defines the corresponding compliance criteria that shall be used by system installers and ECC-Raters.

p.340Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.341