p.2782025 Joint Appendices
Equation text: Vp x 8.33 x ΔT Qout= t
Needs visual review
p.278Qout is the output heating capacity of the HPPH
p.278Vp is the pool volume in gallons
p.2788.33 is the weight of a gallon of water at 62°F in pounds per gallon
p.278ΔT is the pool temperature rise in °F, and shall not exceed 10°F
p.278t is the time needed for the HPPH to achieve the 10 °F degree rise in hours and shall not exceed 17.5 hours
p.278JA16.4 On-site Renewable or Recovered Energy
p.278The mechanical engineer shall provide documentation that a on-site renewable source and/or on-site recovery source provides at least 60 percent of the calculated annual energy consumption of the pool and/or spa heater. The documentation shall be submitted together with the Certificate of Installation for the pool and/or spa heater.
p.278Appendix JA16 – Criteria for Pool and Spa Heating Systems