p.5162025 Nonresidential Appendices Default Visible Transmittance, VT
p.516Equation NA6-3 - VT of Center of Glass (COG) calculation
p.516VTT = VTF x VTC
p.516VTT = Is the Total Performance of the fenestration including glass and frame
p.516VTF = 0.53 for projecting windows, such as casement and awning windows
p.516VTF = 0.67 for operable or sliding windows
p.516VTF = 0.77 for fixed or non-operable windows
p.516VTF= 0.88 for curtain wall/storefront, Site-built and manufactured non-curb mounted skylights
p.516VTF = 1.0 for Curb Mounted manufactured Skylights
p.516VTC = Center of glass VT is calculated in accordance with NFRC 200 Section 4.5.1.1 or NFRC 202 for Translucent Products or NFRC 203 for Tubular Daylighting Devices and Hybrid Tubular Daylighting Devices or ASTM E972 (http://www.nfrc.org/software.aspx)
p.516Responsibilities for Compliance
p.516This section describes the responsibilities of energy consultants, designers, architects, builders, installers, and enforcement agencies when using the procedures of this appendix.
p.516NA6.5.1 Energy Consultants, Designers, Architects
p.516The person with responsibility for preparing the compliance documentation shall establish the inputs from the following:
p.516(a) The center of glass U-factor, SHGC and VT shall be taken from manufacturers’
p.516literature and determined using methods consistent with NFRC 100, NFRC 200, NFRC 202 and NFRC 203 procedures.
p.516(b) The frame type (Metal, Metal Thermal Break, Non-metal) shall be verified from
p.516manufacturers’ literature and through observations of frame sections provided by the manufacturer.
p.516For the Prescriptive Overall Compliance Method, the calculated values shall be entered on the prescriptive Certificate of Compliance form. In addition, the Fenestration Certificate of Compliance Label Certificate must be also filled and located at the project site location in according to Reference Nonresidential Appendix NA7.
p.516For the Performance Compliance Approach, the calculated values shall be entered and documented on the Performance Certificates of Compliance. In addition, the Fenestration Certificate of Compliance Label Certificate must be filled and located at the project site location in according to Reference Nonresidential Appendix NA7.
p.516Appendix NA6– Alternate Default Fenestration Procedure to Calculate Thermal Performance