JA4.1.1 Introduction

p.83JA4.1 Scope and Purpose

p.83JA4.1.1 Introduction

p.83The values in this appendix must be used for all residential and nonresidential prescriptive compliance calculations. California Energy Commission approved compliance software may make adjustments to the values in these tables using procedures described in this appendix.

p.83The data tables are organized first by roofs, walls, and floors. For each, the data is further organized by construction type, beginning with wood framed construction, followed by metal framed construction, concrete and special construction assemblies. Each table features a letter/number coordinate system (shaded in gray) that can be used as an identifier for each value, i.e. 4.2.1-A10 indicates Table 4.2.1, Column A, Row 10. Construction assembly descriptions shall be concatenated first by row and then by column. For example, the descriptions of 4.2.1.-A20 and 4.3.1-H3 and shall be as follows (abbreviations are acceptable):

p.83Wood Framed Attic, Trusses@24 inch. OC, R-30 attic insulation, No continuous insulation Wood Framed Wall, Wd 2x4 @16 inch OC, R-13 cavity insulation, R-14 continuous insulation

p.83The R-value representing the component(s) of a construction assembly may be rounded to the nearest whole R-value. If a construction assembly is not adequately represented in the tables below, the permit applicant or the manufacturer of the product may request the California Energy Commission approve alternative U-factors for the construction assembly. The California Energy Commission Executive Director will grant such approval, after reviewing submittals and supporting information from the applicant and the merits of the information to support the intended use. Acceptable calculation methods for determining a construction component’s R-value or overall assembly U-factor are based on ASHRAE Handbook of Fundamental procedures, such as:

p.83(a) Testing: Guarded Hot Plate (ASTM C177)

p.83Heat Flow Meter (ASTM C518)

p.83Hot Box Apparatus (ASTM C1363)

p.83(b) Series/Parallel Path Calculation Method for wood framed assemblies of

p.83roof/ceilings, walls (above and below grade), and floors.

p.83(c) Modified Zone Method for roof/ceilings, walls, and floor constructions that have

p.83metal framing.

p.83New component(s) of a construction assembly approved by the Executive Director will be published as an addendum to this appendix for use by all compliance authors. Addenda may consist of new tables or additional rows or columns to existing tables.

p.83Appendix JA4 – U-factor, C-factor, and Thermal Mass Data