RA3.7.1 Purpose and Scope

p.4302025 Residential Appendices verified as a model certified to the Energy Commission as qualified for credit as a DWHR unit(s).

p.430(b) The installation configuration (e.g., equal flow, unequal flow to the water heater, or

p.430unequal flow to the showers) and the percent of served shower fixtures shall match the compliance documents.

p.430(c) For water heating system serving a single dwelling, the DWHR system shall, at the

p.430minimum, recover heat from the master bathroom shower and must at least transfer that heat either back to all the respective showers or the water heater.

p.430(d) For central water heating system serving multiple dwellings, the DWHR system shall, at

p.430the minimum, recover heat from half the showers located above the first floor and must at least transfer that heat either back to all the respective showers or the water heater.

p.430(e) The DWHR unit(s) shall be installed within 1 degrees of the rated slope. Sloped DWHR

p.430shall have a minimum lengthwise slope of 1 degree. The lateral level tolerance shall be within plus or minus 1 degree.

p.430(f) The installation shall comply with any applicable California Plumbing Code requirements.

p.430RA3.7 Field Verification and Diagnostic Testing of Mechanical Ventilation Systems

p.430RA3.7.1 Purpose and Scope

p.430RA3.7 contains procedures for verification of heat recovery efficiency and fan efficacy, and for measuring the airflow rate for mechanical ventilation systems.

p.430RA3.7 is applicable to mechanical ventilation systems in residential dwelling units.

p.430RA3.7 provides required procedures for installers, ECC-raters and others who are required to perform field verification of mechanical ventilation systems for compliance with Part 6.

p.430Table RA3.7-1 – Summary of Verification and Diagnostic procedures

DiagnosticDescriptionProcedure
Whole-Building Mechanical Ventilation AirflowVerification of whole-building ventilation system airflow rate. Continuous OperationRA3.7.4.1
Whole-Building Mechanical Ventilation AirflowVerification of whole-building ventilation system airflow rate. Intermittent OperationRA3.7.4.2
Kitchen Local Mechanical ExhaustVerification of vented range hood airflow rate or capture efficiencyRA3.7.4.3

p.430– Residential Field Verification and Diagnostic Test Protocols