p.4312025 Residential Appendices
| Diagnostic | Description | Procedure |
|---|---|---|
| Diagnostic | Description | Procedure |
| Heat Recovery Ventilation (HRV) or Energy Recovery Ventilation (ERV) Rated Performance Verification | Verification of the HRV/ERV fan efficacy (W/cfm) or heat recovery efficiency. | RA3.7.4.4 |
p.431RA3.7.2 Instrumentation Specifications
p.431The instrumentation for the air distribution diagnostic measurements shall conform to the following specifications:
p.431RA3.7.2.1 Pressure Measurements
p.431All pressure measurements shall be measured with measurement systems (i.e., sensor plus data acquisition system) having an accuracy equal to or better than ± 1% of pressure reading or ± 0.2 Pa (0.0008 inches water) (whichever is greater). All pressure measurements within the duct system shall be made with static pressure probes such as Dwyer A303 or equivalent.
p.431RA3.7.2.2 Airflow Rate Measurements
p.431All measurements of ventilation fan airflow rate shall be made with an airflow rate measurement apparatus (i.e., sensor plus data acquisition system) having an accuracy equal to or better than ± 10% of reading. The apparatus shall have an accuracy specification that is applicable to the airflow rates that must be verified utilizing the procedures in Section RA3.7.4. Airflows shall be measured at the mechanical ventilation fan’s inlet terminals/grilles or outlet terminals/grilles.
p.431RA3.7.2.3 Calibration
p.431All instrumentation used for mechanical ventilation system airflow rate diagnostic measurements shall be calibrated according to the manufacturer’s calibration procedure to ensure the airflow measurement apparatus conforms to the accuracy requirement specified in Section RA3.7.2.2.
p.431RA3.7.3 Diagnostic Apparatus for Measurement of Ventilation System Airflow
p.431Ventilation system airflow rate shall be measured using one of the apparatuses listed in Section RA3.7.3. The apparatus shall produce airflow rate measurements that conform to the accuracy requirements specified in Section RA3.7.2 for measurements of residential mechanical ventilation system airflow at system inlet or outlet terminals, grilles, or registers for single or multiple branch ventilation duct systems.
p.431The airflow rate measurement apparatus manufacturers shall publish in their product documentation, specifications for how their airflow measurement apparatuses are to be used for accurately measuring residential mechanical ventilation system airflow at system inlet or outlet terminals, grilles, or registers of single or multiple branch ventilation systems.
p.431The airflow measurement apparatus manufacturers shall certify to the Energy Commission that use of the apparatus in accordance with the specifications given in the manufacturer's product
p.431Appendix RA3– Residential Field Verification and Diagnostic Test Protocols