RA3.7.3.1 Residential Mechanical Exhaust Airflow Measurement Device

p.4322025 Residential Appendices documentation will produce measurement results that are within the accuracy required by Section RA3.7.2.2.

p.432For the airflow measurement apparatuses that are certified to the Commission as meeting the accuracy required by Section RA3.7.2.2, the following information shall be posted on the Energy Commission website, making the information available to all people involved in the airflow verification compliance process:

p.432(a) The product manufacturers' model numbers for the airflow measurement apparatuses.

p.432(b) The product manufacturers' product documentation that gives the specifications for use

p.432of the airflow measurement apparatuses to accurately measure residential mechanical ventilation system airflow at system inlet or outlet terminals, grilles, or registers of single or multiple branch ventilation systems.

p.432A manufacturer's certification to the Commission of the accuracy of the airflow measurement apparatus, and submittal to the Commission of the product documentation that specifies the proper use of the airflow measurement apparatus to produce accurate airflow rate measurements shall be prerequisites for allowing the manufacturer's airflow measurement apparatus to be used for conducting the system airflow verification procedures in Section RA3.7 for demonstrating compliance with Part 6.

p.432RA3.7.3.1 Residential Mechanical Exhaust Airflow Measurement Device

p.432A flowmeter designed for measurement of residential exhaust airflows that meets the applicable instrument accuracy specifications in RA3.7.2 may be used to measure the mechanical exhaust ventilation airflow.

p.432RA3.7.3.2 Powered Flow Capture Hood Airflow Measurement Device

p.432A powered and pressure balanced flow capture hood (subsequently referred to as a Powered Flow Hood3) that has the capability to balance the flow capture static pressure difference between the room and the flow capture hood enclosure to 0.0 ± 0.2 Pa (0.0008 inches water) and meets the applicable instrumentation specifications in Section RA3.7.2 may be used to verify the ventilation airflow rate if the powered flow hood has a flow capture area at least as large as the ventilation system inlet or outlet, terminal, register, or grille in all dimensions. The fan adjustment needed to balance the flow capture static pressure difference between the room and the flow capture hood enclosure to 0.0 ± 0.2 Pa (0.0008 inches water) shall be provided by either an automatic control or a manual control operated in accordance with the apparatus manufacturer's instructions specified in the manufacturer's product documentation.

p.432RA3.7.3.3 Traditional Flow Capture Hood

p.432A traditional flow capture hood4 meeting the applicable instrumentation specifications in Section RA3.7.2 may be used to verify the ventilation system airflow rate if the non-powered flow hood

p.4323 Also known as "active" flow hood, or "fan assisted" flow hood.

p.4324 Also known as “non-powered flow hood, "standard" flow hood, "commercially available" flow hood, or "passive" flow hood.

p.432– Residential Field Verification and Diagnostic Test Protocols