p.179JA6.3 Economizer Fault Detection and Diagnostics Certification Submittal Requirements
p.179Title 24, Part 6, Section 120.2(i) requires that economizer FDD functions be installed on air-cooled unitary air conditioning systems with an air handler mechanical cooling capacity over 33,000 Btu/hr cooling capacity, with the ability to detect the faults specified in Section 120.2(i). Each air conditioning system manufacturer, controls supplier, or FDD supplier of stand-alone or integrated FDD systems used to fulfill economizer fault detection and diagnostics requirements shall certify that their FDD analytics conform to the FDD requirements of Title 24, Part 6, Section 120.2(i)1 – 120.2(i)7 in a written letter to the California Energy Commission. The declaration at the end of this section shall be used in the letter submitted to the California Energy Commission.
p.179JA6.3.1 Information that shall be included with the Declaration
p.179The air conditioning system manufacturer, controls supplier, or FDD supplier provides evidence as shown below:
p.179(a) The following temperature sensors are permanently installed to monitor system
p.179operation:
p.179i. Outside air. ii. Supply air. iii. Return air, when required for differential economizer operation.
p.179Evidence: Photograph or schematic of all required sensors indicating their recommended mounting instructions.
p.179(b) Temperature sensors have an accuracy of ±2°F over the range of 40°F to 80°F
p.179Evidence: Photocopy of sensor specification.
p.179(c) The controller is capable of providing system status by indicating the following:
p.179i. Free cooling available. ii. Economizer enabled. iii. Compressor enabled. iv. Heating enabled, if applicable.
p.179v. Mixed air low limit cycle active. vi. The current value of each sensor.
p.179Evidence: Laboratory test: describe how the mode is simulated and the wording used to indicate the status.
p.179(d) The unit controller is capable of manually initiating each operating mode so that
p.179the operation of compressors, economizers, fans, and heating system, if applicable, can be independently tested and verified.
p.179Evidence: Photocopy of controller manual showing instructions for manually initiating each operating mode.
p.179(e) The unit controller is capable of reporting faults one of the following ways:
p.179i. To an Energy Management Control System regularly monitored by
p.179facility personnel, or;
p.179Appendix JA6 – HVAC System Fault Detection and Diagnostic Technology