p.180ii. Annunciated locally on one or more zone thermostats, or on a device
p.180within five (5) feet of zone thermostat(s), clearly visible, at eye level, and meeting the following requirements:
p.1801. On the thermostat, device, or an adjacent written sign, display instructions to contact appropriate building personnel or an HVAC technician.
p.1802. In buildings with multiple tenants, the annunciation shall either be within property management offices, or in common space accessible by the property or building manager.
p.180iii. To a fault management application which automatically provides
p.180notification of the fault to a remote HVAC service provider.
p.180Evidence: Supplier’s description of how they comply, and supporting documentation such as a photocopy of controller manual or photograph of fault management application, zone thermostat, or other device showing indication of a fault. (f) The unit control is capable of detecting the following faults:
p.180i. Air temperature sensor failure/fault. ii. Not economizing when it should. iii. Economizing when it should not. iv. Damper not modulating.
p.180v. Excess outdoor air.
p.180JA6.3.2 Fault Detection Test Specifications
p.180To provide evidence that the required faults are detected by the FDD functionality, the FDD Provider shall perform a No-Fault and Fault test for each of the tests in Table 1. A pre-defined Test Procedure such as the one provided in the example shown in Table 2 could be used to fill out Table 1.
p.180Appendix JA6 – HVAC System Fault Detection and Diagnostic Technology