| Table JA6.3-1 – | Sample of a completed fault test | |||||
|---|---|---|---|---|---|---|
| Tests | Air temperatur e sensor failure/fault | Not Economizi ng when it should | Economizi ng when it Should not | Damper not modulating | Excess outdoor air | |
| 1. Damper is Stuck Open | NA | NA | X | X | X | |
| 2. Damper Stuck at Minimum | NA | X | NA | X | NA | |
| 3. Bad or Unplugged Actuator | NA | X | X | X | NA | |
| 4. Sensor Hard Failure | X | X | X | NA | X | |
| 5. Actuator Mechanically Disconnecte d | NA | X | X | X | X | |
| k. l. A Table | Name and contact information of company personnel in charge mapping from the manufacturer’s alarm description to what 24 similar to Table 1. JA6.3-2 - Sample Test Procedure | of certification. is required by Title | |
| Step | Description | Purpose | |
| 1 | Close the economizer damper fresh air blades, then secure the blades in a manner that prevents opening. | Test alarm response when “Damper Stuck at Minimum” |
| Step | Description | Purpose | |
|---|---|---|---|
| 14 | Reconnect the damper actuator to the damper blade assembly. Verify the fault(s) have cleared and normal economizer operation has resumed. | NA | |
| 15 | Simulate conditions necessary to generate system status of “Free cooling available”. Record text of annunciated status. | Test for System Status Capability | |
| 16 | Simulate system conditions necessary to generate system status of “Economizer enabled”. Record text of annunciated status. | NA | |
| 17 | Simulate system conditions necessary to generate system status of “Compressor enabled”. Record text of annunciated status. | NA | |
| 18 | If equipped with a heating system, simulate system conditions necessary to generate system status of “Heating enabled”. Record text of annunciated status. | NA | |
| 19 | Simulate system conditions necessary to generate system status of “Mixed air low limit cycle active”. Record text of annunciated status. | NA |
| 3 | Release the blades and allow the economizer damper to modulate open. Verify the annunciated fault(s) have cleared. | NA |
| 4 | Open fully the economizer damper fresh air blades, then secure the blades in a manner that prevents closing. | Test alarm response when “Damper is Stuck Open” |
p.181JA6.3.3 Reporting of Test Results
p.181The results of each test shall be provided in a report using a standard test results reporting format that provides the following information for each test:
| 6 | Release the blades and allow the economizer damper to modulate. Verify the annunciated fault(s) have cleared. | NA | |
| 7 | Disconnect 1 sensor and verify the fault(s) specified in Table 1 are detected. Record the annunciated fault(s) and fault text. | Test alarm response when “Sensor Hard Failure” | |
| 8 | Reconnect the sensor and verify that the annunciated fault(s) have cleared. | NA | |
| 9 | Repeat steps 7 – 8 for each available sensor. | NA | |
| 10 | Electrically disconnect the damper actuator and verify the fault(s) specified in Table 1 are detected. Record annunciated fault(s) and fault text. | Test alarm response when “Bad or Unplugged Actuator” | |
| 11 | Reconnect the damper actuator. Verify the fault(s) have cleared and normal economizer operation has resumed. | NA | |
| 12 | Mechanically disconnect the damper actuator from the damper blade assembly. | Test alarm response when “Actuator Disconnected” | |
| 13 | Simulate conditions such that the damper actuator would be moving the damper blades. Verify the fault(s) specified in Table 2 are detected. Record annunciated fault(s) and fault text. | NA |
p.181a. Organization and individual conducting the test.
p.181b. Time, Date, and Location of test.
p.181c. Make and model of unit/control tested.
p.181d. Range of models represented by test.
p.181e. Test procedure used, including description of the method for imposing fault with
p.181repeatability.
p.181f. Test driving Conditions (outdoor air temperature, return air temperature or enthalpy
p.181as required by the type of high limit control being used).
p.181g. Results of the test: Alarms generated.
p.181h. Provide a bill of materials for the configuration that is being certified.
p.181i. The FDD supplier shall describe any special field or data verifications that are
p.181required for the particular FDD analytics (beyond those included in Acceptance Test requirements).
p.181j. Sample of documentation that would accompany each qualifying set of FDD
p.181analytics.
p.181Appendix JA6 – HVAC System Fault Detection and Diagnostic Technologyp.182
p.182Appendix JA6 – HVAC System Fault Detection and Diagnostic Technologyp.183
p.183Appendix JA6 – HVAC System Fault Detection and Diagnostic Technology