p.1662025 Joint Appendices
p.1702025 Joint Appendices Table 4.5.3 – Rules for Calculating Mass Thermal Properties From Published Values
p.169Table 4.5.2 – Physical Properties of Materials (Continued)
p.166JA4.5 Miscellaneous Construction
p.168value
| Code | Description | R- value | Thicknes s | Conductivit y | Densit y | Specific Heat |
|---|---|---|---|---|---|---|
| AR02 | Asphalt Shingle & Siding | 0.44 | NA | NA | 70.0 | 0.35 |
| BP01 | Building Paper, Permeable Felt | 0.06 | NA | NA | NA | NA |
| PW0 3 | Plywood 1/2 in. | 0.63 | 0.0417 | 0.0667 | 34.0 | 0.29 |
| GP01Gypsum Board 1/2 in. | 0.45 | 0.0417 | 0.0926 | 50.0 | 0.26 | |
| BR01 | Built-up Roofing 3/8 in. | 0.33 | 0.0313 | 0.0939 | 70.0 | 0.35 |
| PW0 5 | Plywood 3/4 in. | 0.94 | 0.0625 | 0.0667 | 34.0 | 0.29 |
| PW0 4 | Plywood 5/8 in. | 0.78 | 0.0521 | 0.0667 | 34.0 | 0.29 |
| CP01 | Carpet with Fibrous Pad | 2.08 | NA | NA | NA | 0.34 |
| PB01 | Particle Board Low Density 3/4 in. | 1.39 | 0.0625 | 0.0450 | 75.0 | 0.31 |
| SC01 | Stucco 1 in. | 0.20 | 0.0833 | 0.4167 | 116.0 | 0.20 |
| WD0 5 | Wood, Soft 4 in. | 5.00 | 0.3333 | 0.0667 | 32.0 | 0.33 |
| WD1 1 | Wood, Hard 3/4 in. | 0.68 | 0.0625 | 0.0916 | 45.0 | 0.30 |
| - CC03 | Heavy Wt. Dried Aggregate 4 in. | 0.44 | 0.3333 | 0.7576 | 140.0 | 0.20 |
| CC14Heavy Wt. Undried Aggregate 4 in. | 0.32 | 0.3333 | 1.0417 | 140.0 | 0.20 | |
| AC02 | 1/2 in. Acoustic Tile | 1.26 | 0.0417 | 0.0330 | 18.0 | 0.32 |
| AL33 | Air Layer 4 in. or more, Horizontal Roof | 0.92 | 1.0000 | 0.4167 | 120.0 | 0.20 |
| CP01 | Carpet with Fibrous Pad | 2.08 | NA | NA | NA | 0.34 |
| Code | Description | R- value | Thicknes s | Conductivit y | Densit y | Specific Heat |
| Custo m | Concrete | 0.11 | NA | NA | 144.0 | 0.20 |
| Custo m | Light Weight CMU | 0.35 | NA | NA | 105.0 | 0.20 |
| Custo m | Medium Weight CMU | 0.35 | NA | NA | 115.0 | 0.20 |
| Custo m | Normal Weight CMU | 0.35 | NA | NA | 125.0 | 0.20 |
| Custo m | Earth (Soil) | 3.00 | 1.5000 | 0.5000 | 85.0 | 0.20 |
| Custo m | Logs 6 in. | 7.50 | 0.5000 | 0.0667 | 32.0 | 0.33 |
| Custo m | Logs 8 in. | 10.00 | 0.6667 | 0.0667 | 32.0 | 0.33 |
| Custo m | Logs 10 in. | 12.49 | 0.8333 | 0.0667 | 32.0 | 0.33 |
| Custo m | Logs 12 in. | 14.99 | 1.0000 | 0.0667 | 32.0 | 0.33 |
| Custo m | Logs 14 in. | 17.49 | 1.1667 | 0.0667 | 32.0 | 0.33 |
| Custo m | Logs 16 in. | 19.99 | 1.3333 | 0.0667 | 32.0 | 0.33 |
| Custo m | Earth 12 in. | 2.00 | 1.0000 | 0.5000 | 85.0 | 0.20 |
| Custo m | Vented crawlspace | 6.00 | NA | NA | NA | NA |
| Custo m | 7/8" layer of stucco of R 0.18 | 0.18 | 0.0729 | 0.4167 | 116.0 | 0.20 |
| Custo m | Straw bale | 30.00 | NA | NA | NA | NA |
| Custo m | Acoustic tile + Metal | 0.50 | 0.0417 | 0.0330 | 18.0 | 0.32 |
| Custo m | OSB 7/16 in. | 0.44 | 0.4375 | 0.0667 | 34.0 | 0.29 |
| Property | Units | Rule for Calculation |
|---|---|---|
| Heat Capacity (HC) | Btu/ºF-ft² | From Table 4.3.5, Table 4.3.6, or Table 4.3.7 |
| U-factor | Btu/h-ºF ft² | From Table 4.3.5, Table 4.3.6, or Table 4.14 |
| C-factor | Btu/h-ºF ft² | From Table 4.3.5, Table 4.3.6, or Table 4.3.7 |
| Thickness (T) | Ft | From Table 4.3.5, Table 4.3.6, or Table 4.3.7 |
| Specific Heat (SH) | Btu/ºF-lb | Assume that the specific heat of all concrete and masonry materials is 0.20 Btu/ºF-lb and that the specific heat of wood or straw (see Table 4.3.11 and Table 4.3.12) is 0.39 Btu/ºF-lb. |
| Weight (W) | lb/ft² | Divide the HC by the assumed specific heat. Wall weight is used with the low-rise residential standards to define a high mass wall. |
| Density (D) | lb/ft³ | Multiply the weight (as calculated above) by the thickness (T) |
| Conductivity (C) | Btu/h-ºF ft | Divide the published C-factor by the thickness (T). When only a U-factor is published, calculate the C-factor by assuming an exterior air film of 0.17 and an interior air film of 0.68. |
p.169value
| Description | U-factor (Btu/ºF-ft²) |
|---|---|
| Uninsulated single-layer metal swinging doors or non-swinging doors, including single-layer uninsulated access hatches and uninsulated smoke vents: | 1.45 |
| Uninsulated double-layer metal swinging doors or non- swinging doors, including double-layer uninsulated access hatches and uninsulated smoke vents: | 0.70 |
| Insulated metal swinging doors, including fire-rated doors, insulated access hatches, and insulated smoke vents: | 0.50 |
| Wood doors, minimum nominal thickness of 1-3/4 in. (44 mm), including panel doors with minimum panel thickness of 1-1/8 in. (28 mm), and solid core flush doors, and hollow core flush doors: | 0.50 |
| Any other wood door: | 0.60 |
| Uninsulated single layer metal roll up doors including fire rated door | 1.45 |
| Insulated single layer metal sectional doors, minimum insulation nominal thickness of 1-3/8 inch; expanded polystyrene (R-4 per inch). | 0.179 |
p.166Source: ASHRAE 90.1-2007, Section A7.
p.169Custo m
p.169Custo m
p.1697/8" layer of stucco of R 0.18 0.18 0.0729 0.4167 116.0 0.20
p.169Custo m
p.169Straw bale 30.00 NA NA NA NA
p.169Custo m
p.169Acoustic tile + Metal 0.50 0.0417 0.0330 18.0 0.32
p.169Custo m
p.169OSB 7/16 in. 0.44 0.4375 0.0667 34.0 0.29
p.166Appendix JA4 – U-factor, C-factor, and Thermal Mass Datap.167
p.168Appendix JA4 – U-factor, C-factor, and Thermal Mass Datap.169
p.169Appendix JA4 – U-factor, C-factor, and Thermal Mass Datap.170
p.170Appendix JA4 – U-factor, C-factor, and Thermal Mass Data