JA4.4 Floors and Slabs (part 2 of 2)

p.1642025 Joint Appendices Assumptions: Data of this table is taken from the ASHRAE/IESNA Standard 90.1-2004, Appendix A.

p.165specified. Vertical insulation is continuous insulation that is applied directly to the slab exterior, extending downward from the top of the slab for the distance specified. Fully insulated slab is continuous insulation that extends downward from the top to the slab and along the entire perimeter and completely covers the entire area under the slab.

p.163Insulation Description

Table 4.4.7 – F-Factors for Unheated Slab-on-Grade Floors p.163 Download CSV
Rated R-Value of InsulationNone12 in. horiz.24 in. horiz.36 in. horiz.48 in. horiz.12 in. vert.24 in. vert.36 in. vert.48 in. vert.Fully insul. slab
R-00.73NANANANANANANANANA
R-5NA0.720.70.680.670.610.580.560.540.46
R-7.5NA0.710.70.670.650.60.560.530.510.41
R-10NA0.710.70.660.640.580.540.510.480.36
R-15NA0.710.690.660.630.570.520.480.450.3
R-20NANANANANA0.5670.510.4720.4340.261
R-25NANANANANA0.5650.5050.4640.4240.233
R-30NANANANANA0.5640.5020.460.4190.213
R-35NANANANANANANANANA0.198
R-40NANANANANANANANANA0.186
R-45NANANANANANANANANA0.176
R-50NANANANANANANANANA0.168
R-55NANANANANANANANANA0.161
Rated R- Value of InsulationNone12 in. horiz.24 in. horiz.36 in. horiz.48 in. horiz.12 in. vert.24 in. vert.36 in. vert.48 in. vert.Fully insul. slab
R-01.35NANANANANANANANANA
R-5NA1.311.281.241.21.060.990.950.910.74
R-7.5NA1.311.271.211.171.020.950.890.850.64
R-10NA1.31.261.21.1310.90.840.780.55
R-15NA1.31.251.181.110.980.860.790.720.44
R-20NANANANANA0.9680.8430.7620.6880.373
R-25NANANANANA0.9640.8320.7470.6710.326
R-30NANANANANA0.9610.8270.740.6590.296
R-35NANANANANANANANANA0.273
R-40NANANANANANANANANA0.255
R-45NANANANANANANANANA0.239
R-50NANANANANANANANANA0.227
R-55NANANANANANANANANA0.217

p.164Table 4.4.8 – F-Factors for Heated Slab-on-Grade Floors

p.164Insulation Description

p.163Note: These values are used for slab edge conditions with and without carpet.

p.165Assumptions: Data of this table is taken from the ASHRAE/IESNA Standard 90.1-2004, Appendix A.

p.164Note: These values are used for slab edge conditions with and without carpet.

Figure 4.4.7 – Unheated Slab-on-Grade Floor
Figure 4.4.7 – Unheated Slab-on-Grade Floor — p.163
Figure 4.4.8 – Heated Slab-on-Grade Floor
Figure 4.4.8 – Heated Slab-on-Grade Floor — p.164

p.163Horizontal insulation is continuous insulation that is applied directly to the underside of the slab and extends inward horizontally from the perimeter for the distance specified or continuous insulation that is applied downward from the top of the slab and then extends horizontally to the interior or the exterior from the perimeter for the distance specified. Vertical insulation is continuous insulation that is applied directly to the slab exterior, extending downward from the top of the slab for the distance specified. Fully insulated slab is continuous insulation that extends downward from the top to the slab and along the entire perimeter and completely covers the entire area under the slab.

p.164Figure 4.4.8 – Heated Slab-on-Grade Floor

p.164Horizontal insulation is continuous insulation that is applied directly to the underside of the slab and extends inward horizontally from the perimeter for the distance specified or continuous insulation that is applied downward from the top of the slab and then extending horizontally to the interior or the exterior from the perimeter for the distance

p.163Appendix JA4 – U-factor, C-factor, and Thermal Mass Datap.164

p.164Appendix JA4 – U-factor, C-factor, and Thermal Mass Datap.165

p.165Appendix JA4 – U-factor, C-factor, and Thermal Mass Data