p.4292025 Residential Appendices (g) The hot water distribution system piping from the water heater(s) to the fixtures and
p.429appliances must take the most direct path. For example, in a house with more than 1 story and the water heater in the garage, this requirement would exclude running hot water supply piping from the water heater to the attic, and then running the line back down to a first floor point of use.
p.429(h) The ECC-rater shall also verify that the supply portion of each circulation loop, the first
p.429five feet of branches off the loop and the dedicated return line are insulated based on the conductivity range in TABLE 120.3-A, the insulation level shall be selected from the fluid temperature range based on the thickness requirements in TABLE 120.3-A and the insulation shall be installed in accordance with RA3.6.2. Other hot water piping shall meet the requirements of §150.0(j) and be installed in accordance with RA3.6.2. Insulation is not required on the cold water line when it is used as the return.
p.429(i) Verify that sensor controls initiate pump operation by activating one of the sensor
p.429controls and observing that the pump turns on and then shuts off in accordance with one of the two methods listed.
p.4291. After the pump has been activated, the controls shall allow the pump to operate until the water temperature at the thermo-sensor rises not more than 10oF (5.6 oC) above the initial temperature of the water in the pipe, or
p.4292. The controls shall not allow the pump to operate when the temperature in the pipe exceeds 102oF (38.9 oC).
p.429(j) Verify that the controls have a feature that limits pump operation to a maximum of 5
p.429minutes following any activation. This is provided in the event that the normal means of shutting off the pump have failed.
p.429(k) The manufacturer(s) of the recirculation pump and the controls shall provide installation
p.429and operation instructions that provide details of the operation of the pump and controls, and such instructions shall be available at the jobsite for inspection.
p.429RA3.6.8 Reserved
p.429RA3.6.9 Verified Drain Water Heat Recovery System (DWHR-H)
p.429A ECC-rater is required to obtain this credit. All DWHR unit(s) shall be certified to the Energy Commission according to the following requirements:
p.429(a) Vertical DWHR unit(s) shall be compliant with CSA B55.2 and tested and labeled in
p.429accordance with CSA B55.1 or IAPMO IGC 346-2017. Sloped DWHR unit(s) shall be compliant with IAPMO PS 92 and tested and labeled with IAPMO IGC 346-2017.
p.429(b) The DWHR unit(s) shall have a minimum rated effectiveness of 42 percent.
p.429The ECC-rater shall verify that:
p.429(a) The make, model, and CSA B55.1 or IAPMO IGC 346-2017 rated effectiveness of the
p.429DWHR unit(s) shall match the compliance documents. The DWHR unit(s) shall also be
p.429Appendix RA3– Residential Field Verification and Diagnostic Test Protocols