p.4282025 Residential Appendices 2. The controls shall not allow the pump to operate when the temperature in the pipe exceeds 102oF (38.9 oC).
p.428(i) Verify that the controls have a feature that limits pump operation to a maximum of 5
p.428minutes following any activation. This is provided in the event that the normal means of shutting off the pump have failed.
p.428(j) The manufacturer(s) of the recirculation pump and the controls shall provide installation
p.428and operation instructions that provide details of the operation of the pump and controls, and such instructions shall be available at the jobsite for inspection.
p.428RA3.6.7 Verified Demand Recirculation: Sensor Control (RDRsc-H)
p.428Demand controlled recirculation systems shall operate “on-demand”, meaning that pump operation shall be initiated shortly prior to the hot water draw. The recirculation pump can be located external to the water heater or be integral to the water heater. The controls shall operate on the principal of shutting off the pump with a sensed rise in pipe temperature (Delta-T). For this verification process a sensor control is used to activate the pump rather than a manual control.
p.428Verification shall include:
p.428(a) More than one circulation loop may be installed. Each loop shall have its own pump and
p.428controls.
p.428(b) Verify that the pump, demand controls and thermo-sensor are present. Sensor controls
p.428shall be located in the kitchen, bathrooms, and any hot water fixture location that is at least 20 feet (measured along the hot water piping) from the water heater.
p.428(c) Sensor controlled systems may be activated by wired or wireless mechanisms, including
p.428motion sensors, door switches and flow switches.
p.428(d) Verify that sensor controls have standby power of 1 watt or less.
p.428(e) Verify that pump and control placement for the demand recirculation meets one of the
p.428following criteria:
p.4281. When a dedicated return line has been installed the pump, controls and thermo- sensor are installed at the end of the supply portion of the recirculation loop (typically under a sink); or
p.4282. The pump and controls is installed on the return line near the water heater and the thermo-sensor is installed in an accessible location as close to the end of the supply portion of the recirculation loop as possible (typically under a sink), or 3. When the cold water line is used as the return, the pump, demand controls and thermosensor shall be installed in an accessible location at the end of supply portion of the hot water distribution line (typically under a sink).
p.428(f) Verify that a check valve is installed in the recirculation loop to prevent unintentional
p.428circulation of the water (thermo-siphoning) and back flow when the system is not operating. This check valve may be included with the pump.
p.428– Residential Field Verification and Diagnostic Test Protocols