p.3372025 Residential Appendices (e) Minimum air filter face area allowed. For each air filter, divide the air filter design airflow
p.337rate in ft3/min by the maximum allowable face velocity in ft/min. The result is the minimum allowable total air filter face area in ft2 for the air filter. Convert the calculated face area from square feet to square inches by multiplying the face area in square feet by 144.
p.337(f) Installed air filter nominal dimensions. Measure and record the installed nominal length
p.337dimension in inches and nominal width dimension in inches for the side of the filter that is perpendicular to the direction of the airflow through the air filter installed in the return air grille/rack of the indoor unit. If there is more than one filtered return air inlet for the indoor unit, measure and record the length dimension and width dimension of each of the air filters.
p.337(g) Installed air filter face area. For each of the filtered return air inlets for the indoor unit,
p.337multiply the nominal air filter length dimension by the nominal air filter width dimension to calculate the nominal air filter face area in square inches.
p.337(h) Determining compliance. For each of the filtered return air inlets for the indoor unit, if
p.337the installed air filter face area is greater than or equal to the minimum air filter face area allowed as determined in step (e), then the air filter complies. All of the indoor unit air filters that are required be sized and verified according to a face velocity specification shall comply, otherwise the indoor unit does not comply.
p.337RA3.1.4.8 Verification of Air Filter Pressure Drop Rating
p.337When compliance requires field verification to confirm that a ducted system's indoor unit air filter(s) comply with a minimum clean filter pressure drop requirement, the following steps shall be followed. When there is more than one filtered return air inlet for the indoor unit, all of the indoor unit's air filter devices shall be field verified.
p.337(a) Indoor unit design airflow rate. Record the design airflow rate for the indoor unit in CFM
p.337as specified by the system designer. The design airflow rate shall be equal to or greater than the minimum airflow rate required for compliance with the standards. Alternatively, if the design airflow rate for the indoor unit is not available, calculate and record the nominal air handler airflow rate for the indoor unit in accordance with the specifications in RA3.1.4.2.2.
p.337(b) Air filter design airflow rate. For indoor units with only one filtered return air inlet, the air
p.337filter design airflow rate in CFM is equal to the indoor unit design airflow rate determined in step (a). For indoor units with more than one filtered return air inlet, the system designer shall determine what portion of the total indoor unit airflow is equal to the air filter design airflow for each air filter, ensuring that the sum total of all individual air filter design airflow rates is equal to the total indoor unit design airflow rate determined in step (a).
p.337(c) Air filter grille/rack sticker. Standards Section 150.0(m)12Biv requires that air filter
p.337installation locations shall have the air filter design airflow rate, and maximum allowable
p.337Appendix RA3– Residential Field Verification and Diagnostic Test Protocols