p.3362025 Residential Appendices RA3.1.4.4 Verification of Return Duct Design
p.336Verification shall consist of a visual inspection to confirm that the duct design conforms to the criteria given in Table 150.0-B or Table 150.0-C.
p.336RA3.1.4.5 Verification of Air Filter Device Design
p.336Verification shall consist of a visual inspection to confirm that the air filter devices conform to the requirements given in Section 150.0(m)12.
p.336RA3.1.4.6 Verification of Bypass Ducts for Zonally Controlled Forced Air Systems
p.336When a zonally controlled forced air system is installed, a visual inspection shall confirm:
p.336(a) That bypass ducts are not used to deliver conditioned supply air directly to the space
p.336conditioning system return duct airflow; or (b) That the Certificate of Compliance indicates an allowance for use of bypass ducts.
p.336RA3.1.4.7 Verification of Air Filter Sizing According to Face Velocity Specification
p.336When compliance requires verification that a ducted system's indoor unit air filters have been sized in accordance with a maximum face velocity specification, the following procedure shall be used.
p.336(a) Indoor unit design airflow rate. Record the design airflow rate for the indoor unit in CFM
p.336as specified by the system designer. The design airflow rate shall be equal to or greater than the minimum airflow rate required for compliance with the standards. Alternatively, if the design airflow rate for the indoor unit is not available, calculate and record the nominal air handler airflow rate for the indoor unit in accordance with the specifications in RA3.1.4.2.2.
p.336(b) Air filter design airflow rate. Determine the air filter design airflow rate. For indoor units
p.336with only one filtered return air inlet, the air filter design airflow rate in CFM is equal to the indoor unit design airflow rate determined in step (a). For indoor units with more than one filtered return air inlet, the system designer shall determine what portion of the total indoor unit airflow is equal to the air filter design airflow for each air filter, ensuring that the sum total of all individual air filter design airflow rates is equal to the total indoor unit design airflow rate determined in step (a).
p.336(c) Air filter grille/rack sticker. Compare the air filter design airflow rate calculated in step (b)
p.336to the design airflow rate on the filter grille or rack. Standards Section 150.0(m)12Biv requires that air filter installation locations shall have the air filter design airflow rate, and maximum allowable clean-filter pressure drop at the design airflow rate posted on a label/sticker, inside or near the location of the filter grille/rack such that this information will be visible to a person replacing the air filter.
p.336If the air filter installation location does not have the required information marked on a label or sticker, the indoor unit does not comply.
p.336(d) Air filter maximum face velocity allowed. Record the maximum allowable face velocity
p.336value in ft/min required for compliance for each air filter.
p.336Appendix RA3– Residential Field Verification and Diagnostic Test Protocols