RA3.8.2 Instrument Specifications

p.4372025 Residential Appendices • Single family building enclosures

p.437• Multifamily dwelling unit enclosures

p.437RA3.8.2 Instrument Specifications

p.437The instrumentation for the enclosure leakage measurements shall conform to the specifications in RESNET 380 Section 4.1.

p.437RA3.8.3 Enclosure Leakage Measurement Procedures

p.437The enclosure leakage measurement procedure shall conform to the following specifications:

p.437(a) The procedure for preparation of the building or dwelling unit for testing shall conform to

p.437the applicable requirements in RESNET 380 Section 4.2.

p.437(b) The procedure for installation of the test apparatus, and preparations for measurement

p.437shall conform to the applicable requirements in RESNET 380 Section 4.3.

p.437If compliance requires the results of the test to be reported in cubic feet per minute per ft2 of dwelling unit enclosure surface area at 50 Pa (0.2 inch water) (CFM50/ft2 of enclosure), the dwelling unit enclosure interior surface area in ft2 (compartmentalization boundary area) shall be recorded.

p.437(c) The procedure for the conduct of the enclosure leakage test shall conform to the One-

p.437Point Airtightness Test specified in RESNET 380 Section 4.4.1 or the multi-point airtightness test specified in the RESNET 380 Section 4.4.2

p.437RA3.8.4 Determination of Test Results

p.437The results of the test shall be determined as follows:

p.437(a) The leakage airflow in CFM50 if determined by the One-Point Airtightness Test specified

p.437in RESNET 380 Section 4.4.1 shall be adjusted using RESNET 380 Section 4.5.1, equation (5a).

p.437(b) If compliance requires the results of the test to be reported in air changes per hour at 50

p.437Pa (0.2 inch water) (ACH50), the leakage results determined by RESNET 380 Section 4.5.1, equation (5a) shall be converted to ACH50 using RESNET 380 Section 4.5.2, equation (7a).

p.437(c) If compliance requires the results of the test to be reported in CFM50/ft2 of enclosed the

p.437leakage results determined by RESNET 380 Section 4.5.1, equation (5a) shall be converted to CFM50/ft2 of enclosure using RESNET 380 Section 4.5.2, equation 10.

p.437RA3.8.5 Determining Compliance

p.437If the applicable value(s) for CFM50, ACH50, or CFM50/ft2 of enclosure determined in Section RA3.8.4 are less than or equal to the enclosure leakage compliance criterion specified by the Standards or the Certificate of Compliance, the enclosure complies. Otherwise, the enclosure does not comply.

p.437Appendix RA3– Residential Field Verification and Diagnostic Test Protocols