NA2.2.4.1.5 Heat Recovery Ventilation (HRV) or Energy Recovery Ventilation (ERV) Rated Performance Verification

p.4942025 Nonresidential Appendices c) The rated airflow value or rated capture efficiency value listed in the HVI, AHAM,

p.4952025 Nonresidential Appendices na1 and pc1 are the closest rated values at 32F for Net Airflow (cfm) and

p.494or other approved directory.

p.495Power Consumed (Watts) respectively that are below the known na value.

p.494d) The sound rating value listed in the HVI, AHAM, or other approved directory.

p.495na2 and pc2 are the closest rated values at 32F for Net Airflow (cfm) and

p.494e) If the value for the rated airflow or rated capture efficiency given in the directory is

p.495Power Consumed (Watts) respectively that are above the known na value.

p.494greater than or equal to the airflow or capture efficiency requirements specified in the Standards, and if the value for the sone rating given in the directory is less than or equal to the sone rating requirements specified in the Standards, then the kitchen range hood complies. Otherwise, the kitchen range hood does not comply. If the kitchen range hood is not listed in the HVI, AHAM, or other CEC- approved directory, then the system does not comply.

p.495c. Divide the value for Power Consumed (Watts) recorded in step b, by

p.495the Net Airflow (cfm) used in step b to determine the Power Consumed.

p.4954. If compliance with a sensible recovery efficiency (SRE) performance rating (%) is required, then determine and record the SRE rating for the installed model using the model details in the energy ratings in the HVI or other CEC-approved directory in accordance with steps a, and b below.

p.494NA2.2.4.1.5 Heat Recovery Ventilation (HRV) or Energy Recovery Ventilation

p.494(ERV) Rated Performance Verification

p.494The verification shall utilize certified performance rating data from the Home Ventilating Institute (HVI) Certified Home Ventilating Products Directory at https://www.hvi.org/hvi­ certified-products-directory/ or another directory of certified product performance ratings approved by the Energy Commission for determining compliance. The verification procedure shall consist of visual inspection of the installed system to verify and record the following information:

p.495a. Record the required ventilation airflow (cfm) for the installed HRV/ERV as

p.495specified on the certificate of compliance.

p.495b. From the energy ratings in the HVI or other CEC approved directory,

p.495determine, and record the rated SRE (%) at 32 degrees F, at the closest Net Airflow (cfm) listed in the directory that is greater than or equal to the ventilation airflow (cfm) required on the certificate of compliance. Alternatively, linear interpolation of the directory ratings at 32 degrees F shall be allowed if the interpolated value is calculated based on a Net Airflow (cfm) that is equal to the ventilation airflow (cfm) required on the certificate of compliance. Interpolation shall be in accordance with equation NA2.2-2. Extrapolation of the directory ratings at 32 degrees F shall not be allowed.

p.4941. Record the manufacturer make and model from the installed system nameplate.

p.4942. Verify the model is listed in the HVI or other CEC-approved directory.

p.4943. If compliance with a fan efficacy performance rating (w/cfm) is required, then determine and record the fan efficacy rating for the installed model using the model details in the energy ratings in the in the HVI or other CEC-approved directory in accordance with steps a, b, and c below.

Equation on PDF page 495: Equation NA2.2-2 sre = sre1 + [(na – na1) / (na2 – na1)] X (sre2 – sre1)

Equation text: Equation NA2.2-2 sre = sre1 + [(na – na1) / (na2 – na1)] X (sre2 – sre1)

Needs visual review

p.495

p.494a. Record the required ventilation airflow (cfm) for the installed HRV/ERV as

p.494specified on the certificate of compliance.

p.495where:

p.494b. From the energy ratings in the HVI or other CEC approved directory,

p.495na is the known value for Net Airflow equal to the ventilation airflow

p.494determine, and record the rated Power Consumed (Watts) at 32 degrees F, at the closest Net Airflow (cfm) listed in the directory that is greater than or equal to the ventilation airflow (cfm) required on the certificate of compliance. Alternatively, linear interpolation of the directory ratings at 32 degrees F shall be allowed if the interpolated value is calculated based on a Net Airflow (cfm) that is equal to the ventilation airflow (cfm) required on the certificate of compliance. Interpolation shall be in accordance with equation NA2.2-1. Extrapolation of the directory ratings at 32 degrees F shall not be allowed.

p.495required on the certificate of compliance,

p.495sre is the unknown value for SRE at 32 degrees F.

p.495na1 and sre1 are the closest rated values at 32F for Net Airflow (cfm) and

p.495SRE respectively that are below the known na value.

p.495na2 and sre2 are the closest rated values at 32F for Net Airflow (cfm) and

p.495SRE respectively that are above the known na value.

Equation on PDF page 494: Equation NA2.2-1 pc = pc1 + [(na – na1) / (na2 – na1)] X (pc2 – pc1)

Equation text: Equation NA2.2-1 pc = pc1 + [(na – na1) / (na2 – na1)] X (pc2 – pc1)

Needs visual review

p.494

p.494where:

p.494na is the known value for Net Airflow equal to the ventilation airflow

p.494required on the certificate of compliance,

p.494pc is the unknown value for Power Consumed (Watts) at 32 degrees F.

p.494Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Proceduresp.495

p.495Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Procedures