p.4932025 Nonresidential Appendices b) Confirm that both the supply side and the exhaust side of the balanced system
p.493operate simultaneously in response to a shared system control.
p.493c) Measure the airflow rate for the exhaust side of the system.
p.493d) Measure the airflow rate for the supply side of the system.
p.493e) Calculate the percent difference between the exhaust and supply airflow rates.
p.493f) Calculate the average of the exhaust and the supply airflow rates.
p.493g) If the exhaust and supply airflow rates are within 20% of each other, and the average
p.493of the exhaust and supply airflow rates is greater than or equal to the airflow rate required by the Standards or the Certificate of Compliance, the balanced ventilation system complies. Otherwise, the system does not comply, and corrective action shall be taken.
p.493h) If the balanced system is an HRV or ERV and compliance with a recovery efficiency
p.493or fan efficacy specification is required, then also perform the verification specified in NA2.2.4.1.5.
p.493NA2.2.4.1.3 Mechanical Ventilation Airflow Rate Measurement - Intermittent
p.493Operation
p.493The Executive Director may approve intermittent mechanical ventilation systems, devices, or controls for use for compliance with field verification and diagnostic testing requirements for mechanical ventilation airflow, subject to a manufacturer providing sufficient evidence to the Executive Director that the installed mechanical ventilation systems, devices, or controls will provide at least the minimum ventilation airflow required by the Standards, and subject to consideration of the manufacturer's proposed field verification and diagnostic test protocol for the ventilation system(s). Ventilation airflow of systems with multiple operating modes shall be tested in all modes designed to comply with the required ventilation airflows.
p.493Approved systems, devices, or controls, and field verification and diagnostic test protocols for intermittent mechanical ventilation systems shall be listed in directories published by the Energy Commission.
p.493NA2.2.4.1.4 Kitchen Local Mechanical Exhaust - Vented Range Hood
p.493Verification
p.493The verification shall utilize certified performance rating data from the Home Ventilating Institute (HVI) Certified Home Ventilating Products Directory at https://www.hvi.org/hvi certified-products-directory/, the Association of Home Appliance Manufacturers (AHAM) Certified Products Directory at https://www.aham.org/AHAM/What_We_Do/Kitchen_Range_Hood_Certification, or another directory of certified product performance ratings approved by the Energy Commission for determining compliance. The verification procedure shall consist of visual inspection of the installed kitchen range hood to verify and record the following information:
p.493a) The manufacturer name and model number.
p.493b) The model is listed in the HVI or AHAM or other approved directory.
p.493Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Procedures