p.4922025 Nonresidential Appendices difference between the room and the flow capture hood enclosure to 0.0 ± 0.2 Pa (0.0008 inches water) and meets the applicable instrumentation specifications in Section NA2.2.2.2 may be used to verify the ventilation airflow rate if the powered flow hood has a flow capture area at least as large as the ventilation system inlet or outlet terminal, register, or grille in all dimensions. The fan adjustment needed to balance the flow capture static pressure difference between the room and the flow capture hood enclosure to 0.0 ± 0.2 Pa (0.0008 inches water) shall be provided by either an automatic control or a manual control operated in accordance with the apparatus manufacturer's instructions specified in the manufacturer's product documentation.
p.492NA2.2.3.3 Traditional Flow Capture Hood
p.492A traditional flow capture hood1F2 meeting the applicable instrumentation specifications in Section NA2.2.2.2 may be used to verify the ventilation system airflow rate if the non- powered flow hood has a capture area at least as large as the ventilation system inlet or outlet terminal, register or grille in all dimensions.
p.492NA2.2.4 Procedures
p.492This section describes the procedures used to verify Mechanical ventilation system airflow.
p.492NA2.2.4.1 Mechanical Ventilation Airflow Rate Measurement - Continuous Operation
p.492If multiple fans are specified to operate simultaneously to provide the total required ventilation airflow, the measurements shall be made with all applicable fans operating simultaneously.
p.492NA2.2.4.1.1 Supply and Exhaust Ventilation Systems
p.492a) A flow measuring device that meets the applicable instrumentation requirements
p.492specified in Section NA2.2.3.2, and NA2.2.3.3 shall be used to measure the ventilation airflow(s).
p.492b) Measure and record the ventilation airflow(s).
p.492c) If the measured total airflow is greater than or equal to the ventilation airflow rate
p.492required by the Standards or the Certificate of Compliance, the mechanical ventilation system complies. Otherwise the mechanical ventilation system does not comply, and corrective action shall be taken.
p.492NA2.2.4.1.2 Balanced Ventilation Systems
p.492a) A flow measuring device that meets the applicable instrumentation requirements
p.492given in Section NA2.2.3.2 and NA2.2.3.3 shall be used to measure the ventilation airflows.
p.4922 Also known as “non-powered flow hood, "standard" flow hood, "commercially available" flow hood, or "passive" flow hood.
p.492Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Procedures