p.4912025 Nonresidential Appendices NA2.2.3 Diagnostic Apparatus for Measurement of Ventilation System Airflow
p.491Ventilation system airflow rate shall be measured using one of the apparatuses listed in Section NA2.2.3. The apparatus shall produce airflow rate measurements that conform to the accuracy requirements specified in Section NA2.2.2 for measurements of high-rise residential mechanical ventilation system airflow at system inlet or outlet terminals, grilles, or registers for single or multiple branch ventilation duct systems.
p.491The airflow rate measurement apparatus manufacturers shall publish in their product documentation, specifications for how their airflow measurement apparatuses are to be used for accurately measuring residential mechanical ventilation system airflow at system inlet or outlet terminals, grilles, or registers of single or multiple branch ventilation systems.
p.491The airflow measurement apparatus manufacturers shall certify to the Energy Commission that use of the apparatus in accordance with the specifications given in the manufacturer's product documentation will produce measurement results that are within the accuracy required by Section NA2.2.2.2.
p.491For the airflow measurement apparatuses that are certified to the Commission as meeting the accuracy required by Section NA2.2.2.2, the following information shall be posted on the Energy Commission website, making the information available to all people involved in the airflow verification compliance process:
p.491(a) The product manufacturers' model numbers for the airflow measurement
p.491apparatuses.
p.491(b) The product manufacturers' product documentation that gives the specifications
p.491for use of the airflow measurement apparatuses to accurately measure high-rise residential mechanical ventilation system airflow at system inlet or outlet terminals, grilles, or registers of single or multiple branch ventilation systems.
p.491A manufacturer's certification to the Commission of the accuracy of the airflow measurement apparatus, and submittal to the Commission of the product documentation that specifies the proper use of the airflow measurement apparatus to produce accurate airflow rate measurements shall be prerequisites for allowing the manufacturer's airflow measurement apparatus to be used for conducting the system airflow verification procedures in Section NA2.2 for demonstrating compliance with Part 6.
p.491NA2.2.3.1 High-Rise Residential Mechanical Exhaust Airflow Measurement Device
p.491A flowmeter designed for measurement of high-rise residential exhaust airflows that meets the applicable instrument accuracy specifications in NA2.2.2.2 may be used to measure the mechanical exhaust ventilation airflow.
p.491NA2.2.3.2 Powered Flow Capture Hood Airflow Measurement Device
p.491A powered and pressure balanced flow capture hood (subsequently referred to as a Powered Flow Hood0F1) that has the capability to balance the flow capture static pressure
p.491Also known as "active" flow hood, or "fan assisted" flow hood.
p.491Appendix NA2 – Nonresidential Field Verification and Diagnostic Test Procedures