SECTION 141.0 – ADDITIONS, ALTERATIONS, AND REPAIRS TO EXISTING NONRESIDENTIAL, AND HOTEL/MOTEL BUILDINGS, TO EXISTING OUTDOOR LIGHTING, AND TO INTERNALLY AND EXTERNALLY ILLUMINATED SIGNS (part 1 of 2)

Scanned crop of table from PDF page 395
NEW OR REPLACEMENT SINGLE ZONE AIR CONDITIONER OR HEAT PUMP REQUIREMENT p.391 Download CSV
Building TypeCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
Retail and groceryNRNRSZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1NRSZHP or SZAC1NR
SchoolSZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1NR
Office, financial institutionNRNRSZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC2SZHP or SZAC1SZHP or SZAC1NRSZHP or SZAC1NR
LibrarySZHP or SZAC1NRSZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1SZHP or SZAC1NR
INSULATION REQUIREMENTS FOR ROOF ALTERATIONS p.390 Download CSV
Climate ZoneContinuous Insulation R-valueU-factor
1-5, 9-16R-230.037, with at least R-10 above deck
6-8R-170.047, with at least R-10 above deck
Roof/Ceiling Insulation Tradeoff for Low-Sloped Aged Solar Reflectance p.389 Download CSV
Aged Solar ReflectanceClimate Zones 6, 7, & 8 U-factorAll Other Climate Zones U-factor
0.62- 0.600.0430.035
0.59-0.550.0410.034
0.54-0.500.0380.031
0.49-0.450.0340.029
0.44-0.400.0320.028
0.39-0.350.0290.026
0.34-0.300.0280.025
0.29-0.250.0260.024
ADDITIONAL FAN POWER ALLOWANCES p.390 Download CSV
AirflowMulti-Zone VAV Systems1 ≤5,000 cfmMulti-Zone VAV Systems1 >5,000 and ≤10,000 cfmMulti-Zone VAV Systems1 >10,000 cfmAll Other Fan Systems ≤5,000 cfmAll Other Fan Systems >5,000 and ≤10,000 cfmAll Other Fan Systems >10,000 cfm
Supply Fan System Additional Allowance0.1350.1140.1050.1390.120.107
Supply Fan System Additional Allowance In Unit with Adapter Curb0.0330.0330.0430.0000.0000.000
Exhaust/ Relief/ Return/ Transfer Fan System Additional Allowance0.070.0610.0540.070.0620.055
Exhaust/ Relief/ Return/ Transfer Fan System Additional Allowance In Unit with Adapter Curb0.0160.0170.0220.0000.0000.000
Altered Vertical Fenestration Maximum U-Factor and Maximum RSHGC p.388 Download CSV
RequirementCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
U-factor0.470.470.580.470.580.470.470.470.470.470.470.470.470.470.470.47
RSHGC0.410.310.410.310.410.310.310.310.310.310.310.310.310.310.310.41