NEW OR REPLACEMENT SINGLE ZONE AIR CONDITIONER OR HEAT PUMP REQUIREMENT p.391 Download CSV
Building Type CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7 CZ 8 CZ 9 CZ 10 CZ 11 CZ 12 CZ 13 CZ 14 CZ 15 CZ 16
Retail and grocery NR NR SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 NR SZHP or SZAC1 NR School SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 NR Office, financial institution NR NR SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC2 SZHP or SZAC1 SZHP or SZAC1 NR SZHP or SZAC1 NR Library SZHP or SZAC1 NR SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 SZHP or SZAC1 NR
INSULATION REQUIREMENTS FOR ROOF ALTERATIONS p.390 Download CSV
Climate Zone Continuous Insulation R-value U-factor
1-5, 9-16 R-23 0.037, with at least R-10 above deck 6-8 R-17 0.047, with at least R-10 above deck
Roof/Ceiling Insulation Tradeoff for Low-Sloped Aged Solar Reflectance p.389 Download CSV
Aged Solar Reflectance Climate Zones 6, 7, & 8 U-factor All Other Climate Zones U-factor
0.62- 0.60 0.043 0.035 0.59-0.55 0.041 0.034 0.54-0.50 0.038 0.031 0.49-0.45 0.034 0.029 0.44-0.40 0.032 0.028 0.39-0.35 0.029 0.026 0.34-0.30 0.028 0.025 0.29-0.25 0.026 0.024
ADDITIONAL FAN POWER ALLOWANCES p.390 Download CSV
Airflow Multi-Zone VAV Systems1 ≤5,000 cfm Multi-Zone VAV Systems1 >5,000 and ≤10,000 cfm Multi-Zone VAV Systems1 >10,000 cfm All Other Fan Systems ≤5,000 cfm All Other Fan Systems >5,000 and ≤10,000 cfm All Other Fan Systems >10,000 cfm
Supply Fan System Additional Allowance 0.135 0.114 0.105 0.139 0.12 0.107 Supply Fan System Additional Allowance In Unit with Adapter Curb 0.033 0.033 0.043 0.000 0.000 0.000 Exhaust/ Relief/ Return/ Transfer Fan System Additional Allowance 0.07 0.061 0.054 0.07 0.062 0.055 Exhaust/ Relief/ Return/ Transfer Fan System Additional Allowance In Unit with Adapter Curb 0.016 0.017 0.022 0.000 0.000 0.000
Altered Vertical Fenestration Maximum U-Factor and Maximum RSHGC p.388 Download CSV
Requirement CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7 CZ 8 CZ 9 CZ 10 CZ 11 CZ 12 CZ 13 CZ 14 CZ 15 CZ 16
U-factor 0.47 0.47 0.58 0.47 0.58 0.47 0.47 0.47 0.47 0.47 0.47 0.47 0.47 0.47 0.47 0.47 RSHGC 0.41 0.31 0.41 0.31 0.41 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.41