Section 160.3 – Mandatory Requirements for Space Conditioning Systems in Multifamily Buildings

p.496iii. Where used to control both comfort heating and comfort cooling, the thermostatic

p.497a. Occupant sensing zone controls shall comply with the occupant sensor ventilation

p.496controls shall meet Items i and ii and shall be capable of providing a temperature range or deadband of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.

p.497control device requirements of Section 160.3(c)5E and allow preoccupancy ventilation requirements of Section 160.3(c)5B; and

p.495Section 160.3 – Mandatory Requirements for Space Conditioning Systems in Multifamily Buildings

p.498G. Automatic demand shed controls. See Section 110.12 for requirements for automatic

p.498demand shed controls.

p.497b. In 5 minutes or less after entering occupied-standby mode as described in Section

p.498H. Economizer Fault Detection and Diagnostics (FDD). All newly installed air handlers with a

p.495Space conditioning systems serving multifamily dwelling units and common use areas shall comply with the applicable requirements of Sections 160.3(a) through 160.3(c).

p.497160.2(c)5:

p.498mechanical cooling capacity over 33,000 Btu/hr and an installed air economizer shall include a stand-alone or integrated Fault Detection and Diagnostics (FDD) system in accordance with Subsections 160.3(a)2Hi through 160.3(a)2Hviii.

p.497I. Automatically set up the operating cooling temperature setpoint by 2°F or more

p.495(a) Controls. Space-conditioning systems serving dwelling units and common use areas in multifamily

p.496iv. Thermostatic controls for all single zone air conditioners and heat pumps shall comply

p.497and set back the operating heating temperature setpoint by 2°F or more; or

p.495buildings shall comply with applicable requirements of Section 160.3(a)1 or 160.3(a)2.

p.496with the requirements of Sections 110.2(c) and 110.12(a) and, if equipped with DDC to the zone level, with the automatic demand shed controls of Section 110.12(b).

p.497II. For multiple zone systems with Direct Digital Controls (DDC) to the zone level,

p.498i. The following temperature sensors shall be permanently installed to monitor system

p.4951. Dwelling unit thermostats. All heating or cooling systems, including heat pumps, not controlled by a central energy management control system (EMCS) shall have a setback thermostat, as specified in Section 110.2(c). 2. Common use area controls. Heating or cooling systems serving common use areas of multifamily buildings shall comply with application requirements of Sections 160.3(a)2A through 160.3(a)2J.

p.497set up the operating cooling temperature setpoint by 0.5°F or more and set back the operating heating temperature setpoint by 0.5°F or more.

p.498operation: outside air, supply air and, when required for differential economizer operation, a return air sensor; and

p.497c. In 5 minutes or less after entering occupied-standby mode, mechanical ventilation

p.498ii. Temperature sensors shall have an accuracy of ±2°F over the range of 40°F to 80°F; and

p.496C. Heat pump controls.

p.497to the zone shall remain off whenever the space temperature is between the active heating and cooling setpoints.

p.498iii. The controller shall have the capability of displaying the value of each sensor; and

p.496All heat pumps with supplementary electric resistance heaters shall be installed with

p.498iv. The controller shall provide system status by indicating the following conditions:

p.496controls that comply with Section 110.2(b).

p.498a. Free cooling available;

p.496D. Shut-off and reset controls for space-conditioning systems. Each space-conditioning

p.498b. Economizer enabled;

p.496system shall be installed with controls that comply with the following:

p.498c. Compressor enabled;

p.496i. The control shall be capable of automatically shutting off the system during periods of

p.496nonuse and shall have:

p.498d. Heating enabled, if the system is capable of heating; and

p.495A. Thermostatic controls for each zone. The supply of heating and cooling energy to each

p.496a. An automatic time switch control device complying with Section 110.9, with an

p.498e. Mixed air low limit cycle active.

p.495space-conditioning zone shall be controlled by an individual thermostatic control that responds to temperature within the zone and that meets the applicable requirements of Section 160.3(a)2B. An energy management control system (EMCS) may be installed to comply with the requirements of one or more thermostatic controls if it complies with all applicable requirements for each thermostatic control.

p.496accessible manual override that allows operation of the system for up to 4 hours; or

p.498v. The unit controller shall allow manual initiation of each operating mode so that the

p.497E. Dampers for air supply and exhaust equipment. Outdoor air supply and exhaust

p.496b. An occupancy sensor; or

p.498operation of cooling systems, economizers, fans and heating systems can be independently tested and verified; and

p.497equipment shall be installed with dampers that automatically close upon fan shutdown.

p.496c. A 4-hour timer that can be manually operated.

p.498vi. Faults shall be reported in one of the following ways:

p.496ii. The control shall automatically restart and temporarily operate the system as required

p.496to maintain:

p.498a. Reported to an Energy Management Control System regularly monitored by facility

p.498personnel.

p.496a. A setback heating thermostat setpoint if the system provides mechanical heating;

p.495i. All zones are also served by an interior cooling system; and

p.496and

p.498b. Annunciated locally on one or more zone thermostats, or a device within five feet of

p.495ii. The perimeter system is designed solely to offset envelope heat losses or gains; and

p.498zone thermostat(s), clearly visible, at eye level and meeting the following requirements:

p.495iii. The perimeter system has at least one thermostatic control for each building

p.495orientation of 50 feet or more; and

p.497F. Isolation area devices. Each space-conditioning system serving multiple zones with a

p.498I. On the thermostat, the device or an adjacent written sign, display instructions to

p.497combined conditioned floor area of more than 25,000 square feet shall be designed, installed and controlled to serve isolation areas.

p.498contact appropriate building personnel or an HVAC technician; and

p.496b. A setup cooling thermostat setpoint if the system provides mechanical cooling.

p.495iv. The perimeter system is controlled by at least one thermostat located in one of the

p.495zones served by the system.

p.498II. In buildings with multiple tenants, the annunciation shall either be within

p.497i. Each zone, or any combination of zones not exceeding 25,000 square feet, shall be a

p.498property management offices or in a common space accessible by the property or building manager.

p.495B. Criteria for zonal thermostatic controls. The individual thermostatic controls required by

p.497separate isolation area.

p.495Section 160.3(a)2A shall meet the following requirements as applicable:

p.497ii. Each isolation area shall be provided with isolation devices, such as valves or dampers

p.498c. Reported to a fault management application that automatically provides notification

p.495i. Where used to control comfort heating, the thermostatic controls shall be capable of

p.496iii. Occupant sensing zone controls. Where the system providing space conditioning also

p.497that allow the supply of heating or cooling to be reduced or shut off independently of other isolation areas.

p.498of the fault to remote HVAC service provider.

p.495being set, locally or remotely, down to 55°F or lower.

p.496provides the ventilation required by Section 160.2(c)3 and includes occupant sensor ventilation control as specified in Section 160.2(c)5E, the occupant sensing zone controls shall additionally comply with the following:p.497

p.498vii. The FDD system shall detect the following faults:

p.495ii. Where used to control comfort cooling, the thermostatic controls shall be capable of

p.497iii. Each isolation area shall be controlled by a device meeting the requirements of Section

p.495being set, locally or remotely, up to 85°F or higher.p.496

p.498a. Air temperature sensor failure/fault;

p.497160.3(a)2Di.p.498

p.495SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS

p.496SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS

p.497SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS

p.498SECTION 160.3 – MANDATORY REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS IN MULTIFAMILY BUILDINGS