7. Design and control requirements for quantities of outdoor air.
Text in this table
SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
B. All variable air volume mechanical ventilation and space-conditioning systems shall include
dynamic controls that maintain measured outside air ventilation rates within 10 percent of the required outside air ventilation rate at both full and reduced supply airflow conditions. Fixed minimum damper position is not considered to be dynamic and is not an allowed control strategy.
C. Measured outdoor air rates of constant volume mechanical ventilation and space-
conditioning systems shall be within 10 percent of the required outside air rate.
8. Air classification and recirculation limitations. Air classification and recirculation limitations of air shall be based on the air classification as listed in Table 160.2-B or Table 160.2-D, in accordance with the following:
A. Class 1 air is air with low contaminant concentration, low sensory-irritation intensity or
inoffensive odor. Recirculation or transfer of Class 1 air to any space shall be permitted; [ASHRAE 62.1:5.13.3.1]
B. Class 2 air is air with moderate contaminant concentration, mild sensory-irritation intensity
or mildly offensive odor (Class 2 air also includes air that is not necessarily harmful or objectionable but that is inappropriate for transfer or recirculation to spaces used for different purposes). Recirculation or transfer of Class 2 air shall be permitted in accordance with Sections 160.2(c)8Bi through 160.2(c)8Bv:
i. Recirculation of Class 2 air within the space of origin shall be permitted [ASHRAE
62.1:5.13.3.2.1].
ii. Recirculation or transfer of Class 2 to other Class 2 or Class 3 spaces shall be permitted,
provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space [ASHRAE 62.1:5.13.3.2.2]; or
iii. Transfer of Class 2 air to toilet rooms [ASHRAE 62.1:5.13.3.2.3]; or
iv. Recirculation or transfer of Class 2 air to Class 4 spaces [ASHRAE 62.1:5.13.3.2.4]; or
v. Class 2 air shall not be recirculated or transferred to Class 1 spaces. [ASHRAE
62.1:5.13.3.2.5]
Exception to Section 160.2(c)8Bv: When using any energy recovery device, recirculation from leakage, carryover or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 2 air shall not exceed 10 percent of the outdoor air intake flow.
C. Class 3 air is air with significant contaminant concentration, significant sensory-irritation
intensity or offensive odor. Recirculation or transfer of Class 3 air shall be permitted in accordance with Sections 160.2(c)8Ci and 160.2(c)8Cii:
i. Recirculation of Class 3 air within the space of origin shall be permitted. [ASHRAE
62.1:5.13.3.3.1]
ii. Class 3 air shall not be recirculated or transferred to any other space. [ASHRAE
62.1:5.13.3.3.2].
Airstreams or Sources[ASHRAE 62.1:Table 6-35.16.1] p.493Download CSV
Description
Air Class
Commercial kitchen grease hoods
4
Commercial kitchen hoods other than grease
3
Hydraulic elevator machine room
2
Refrigerating machinery rooms
3
Kitchen Range Hood Airflow Rates (cfm) and ASTM E3087 Capture Efficiency (CE) RatingsAccording to Dwelling Unit Floor Area and Kitchen Range Fuel Type p.494Download CSV
Dwelling Unit Floor Area (ft2)
Hood Over Electric Range
Hood Over Natural Gas Range
>1500
50% CE or 110 cfm
70% CE or 180 cfm
>1000 - 1500
50% CE or 110 cfm
80% CE or 250 cfm
750 - 1000
55% CE or 130 cfm
85% CE or 280 cfm
<750
65% CE or 160 cfm
85% CE or 280 cfm
Minimum Occupant Load Density and Ventilation Rates for Multifamily Common Use Areas p.491Download CSV
Space Type
Minimum Occupant Load Density (p/1000 ft2)1
Area-based Minimum Ventilation Ra (cfm/ft2)
Air Class
Notes
Bars, cocktail lounges
33
0.2
2
-
Break rooms
33
0.15
1
F
Coffee stations
33
0.15
1
F
Conference/meeting
33
0.15
1
F
Corridors
5
0.15
1
F
Computer (not printing)
5
0.15
1
F
Daycare (through age 4)
14
0.15
2
-
Dining rooms
33
0.15
2
-
Disco/dance floors
100
0.15
2
F
Freezer and refrigerated spaces (<50oF)
0
0
2
E
Game arcades
45
0.15
1
-
Gym, sports arena (play area)
10
0.15
2
E
Health club/aerobics room/weight rooms
10
0.15
2
-
Kitchen (cooking)
3
0.15
2
-
Laundry rooms, central
5
0.15
2
-
Lobbies/pre-function
33
0.15
1
F
Multiuse assembly
33
0.15
1
F
Occupiable storage rooms for dry materials
2
0.15
1
-
Occupiable storage rooms for liquids or gels
2
0.15
2
B
Office space
5
0.15
1
F
Reception areas
5
0.15
1
F
Shipping/receiving
2
0.15
2
B
Spectator areas
33
0.15
1
F
Swimming (deck)
33
0.15
2
C
Swimming (pool)
10
0.15
2
C
Telephone/data entry
33
0.15
1
F
All others
5
0.15
2
-
Demand-Controlled Local Ventilation Exhaust Airflow Rates and Capture Efficiency p.493Download CSV
Application
Compliance Criteria
Enclosed Kitchen or Nonenclosed Kitchen
Vented range hood, including appliance-range hood combinations shall meet either the capture efficiency (CE) or the airflow rate specified in Table 160.2-G, as applicable.
Enclosed Kitchen or Nonenclosed Kitchen
Other kitchen exhaust fans, including downdraft: 300 cfm (150 L/s).