p.487D. Demand control ventilation devices.
p.486ii. The outdoor air that is supplied to all spaces combined is sufficient to meet the
p.486requirements of Section 160.2(c)3 for each space individually.
p.487i. For each system with demand control ventilation (DCV), CO2 sensors shall be installed in
p.4864. Exhaust ventilation. The design exhaust airflow shall be determined in accordance with the requirements in Table 160.2-C. Exhaust makeup air shall be permitted to be any combination of outdoor air, recirculated air or transfer air. [ASHRAE 62.1:6.5.1]
p.487each room that meets the criteria of Section 160.2(c)5C with no less than one sensor per 10,000 ft2 of floor space. When a zone or a space is served by more than one sensor, a signal from any sensor indicating that CO2 is near or at the setpoint within the zone or space shall trigger an increase in ventilation.
p.4865. Operation and control requirements for minimum quantities of outdoor air.
p.487ii. CO2 sensors shall be located in the room between 3 ft and 6 ft above the floor or at the
p.486A. Times of occupancy. The minimum rate of outdoor air required by Section 160.2(c) shall be
p.487anticipated height of the occupants’ heads.
p.486supplied to each space at all times when the space is usually occupied.
p.487iii. Demand ventilation controls shall maintain CO2 concentrations less than or equal to 600
p.487ppm plus the outdoor air CO2 concentration in all rooms with CO2 sensors.
p.487iv. Outdoor air CO2 concentration shall be determined by one of the following:
p.487a. CO2 concentration shall be assumed to be 400 ppm without any direct
p.487measurement; or
p.487b. CO2 concentration shall be dynamically measured using a CO2 sensor located within
p.4874 ft of the outdoor air intake.
p.487v. When the system is operating during hours of expected occupancy, the controls shall
p.486B. Preoccupancy. The lesser of the minimum rate of outdoor air required by Section 160.2(c)
p.487maintain system outdoor air ventilation rates no less than Ra × Az per Equation 160.2-H for each space with a CO2 sensor(s), plus the greater of either the exhaust air rate or the rate required by Section 160.2(c)3 for other spaces served by the system.
p.486or three complete air changes shall be supplied to the entire building during the 1-hour period immediately before the building is normally occupied.
p.486C. Required demand control ventilation. Demand ventilation controls complying with Section
p.487vi. CO2 sensors shall be certified by the manufacturer to be accurate within plus or minus
p.486160.2(c)5D are required for a space with a design occupant density, or a maximum occupant load factor for egress purposes in the CBC, greater than or equal to 25 people per 1000 square feet (40 square feet or less per person) if the system serving the space has one or more of the following:
p.48775 ppm at a 600 and 1000 ppm concentration when measured at sea level and 25°C, factory calibrated, and certified by the manufacturer to require calibration no more frequently than once every 5 years. Upon detection of sensor failure, the system shall provide a signal that resets to supply the minimum quantity of outside air to levels required by Section 160.2(c)3 to the zone serviced by the sensor at all times that the zone is occupied.
p.486ii. modulating outside air control; or
p.486iii. design outdoor airflow rate > 3,000 cfm.
p.487vii. The CO2 sensor(s) reading for each zone shall be displayed continuously, and shall be
p.487recorded on systems with digital direct controls (DDC) to the zone level.
p.487E. Occupied-Standby Zone Controls.
p.487i. Space conditioning zones shall include occupied standby controls complying with Table 160.2-B when all of the following are true:
p.487a. All rooms served by the zone are permitted to have their ventilation air reduced to zero while in occupied-standby mode per Table 160.2-B; and
p.487b. Occupant sensors are required by Section 160.5(b)4Cv and vi; and
p.487c. The zone and ventilation system are not served by pneumatic controls.
p.486SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.487SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY