p.484a system’s thermal conditioning component, provided the system is equipped with ancillary filtration upstream of the system’s thermal conditioning component.
p.484B. Air filter efficiency. The filters shall have a designated efficiency equal to or greater than
p.485B. Location and size of openings. Zones or portions of zones to be naturally ventilated shall
p.484MERV 13 when tested in accordance with ASHRAE Standard 52.2, or a particle size efficiency rating equal to or greater than 50 percent in the 0.30–1.0 μm range, and equal to or greater than 85 percent in the 1.0–3.0 μm range when tested in accordance with AHRI Standard 680; and
p.485have a permanently open airflow path to openings directly connected to the outdoors. The openable area shall be not less than 4 percent of the net occupiable floor area. Where openings are covered with louvers or otherwise obstructed, the openable area shall be based on the net free unobstructed area through the opening. Where interior rooms, or portions of rooms, without direct openings to the outdoors are ventilated through adjoining rooms, the opening between rooms shall be permanently unobstructed and have a free area of not less than 8 percent of the area of the interior room or less than 25 square feet. [ASHRAE 62.1:6.4.1.6]
p.484C. Systems shall be equipped with air filters that meet either Subsection i or ii below.
p.484i. Nominal two inch minimum depth filter(s); or
p.484ii. Nominal one inch minimum depth filter(s) shall be allowed if the filter(s) are sized
p.485C. Control and accessibility. The means to open the required operable opening shall be readily
p.484according to Equation 160.2-A, based on a maximum face velocity of 150 ft per minute.
p.485accessible to building occupants whenever the space is occupied. Controls shall be designed to coordinate operation of the natural and mechanical ventilation systems. [ASHRAE 62.1:6.4.3]
p.484D. Filter racks or grilles shall be gasketed or sealed to eliminate any gaps around the filter to
p.484prevent air from bypassing the filter.
p.485D. Naturally ventilated spaces shall also include a mechanical ventilation system designed in
p.4842. Natural ventilation. Naturally ventilated spaces shall be designed in accordance with Sections 160.2(c)2A through 160.2(c)2D.
p.485accordance with 160.2(c)3.
p.484A. Floor area to be ventilated. Spaces or portions of spaces to be naturally ventilated shall be
p.484located within a distance based on the ceiling height, as specified in i, ii and iii. The ceiling height (H) to be used in i, ii or iii shall be the minimum ceiling height in the space, or for ceilings that are increasing in height as distance from the operable openings is increased, the ceiling height shall be determined as the average height of the ceiling within 20 ft from the operable opening. [ASHRAE 62.1:6.4.1.1]
p.4853. Mechanical ventilation. Occupiable spaces shall be ventilated with a mechanical ventilation system capable of providing an outdoor airflow rate (Vz) to the zone no less than the Equation 160.2-H as described below:
p.484i. Single side opening. For spaces with operable opening on one side of the zone, the
p.484naturally ventilated area shall extend to a distance not greater than two times the height (H) of the ceiling from the openings. [ASHRAE 62.1:6.4.1.3]
Equation text: Vz = The larger of Rp x Pz or Ra × Az (Equation 160.2-H)
Needs visual review
p.484ii. Double side opening. For zones with openings on two opposite sides of the zone, the
p.484naturally ventilated area shall extend between the openings separated by a distance not greater than five times the height of the ceiling. [ASHRAE 62.1:6.4.1.4]
p.485Rp = 15 cubic feet per minute of outdoor airflow per person
p.485Pz = The expected number of occupants. For spaces without fixed seating, the expected
p.484iii. Corner opening. For zones with operable openings on two adjacent sides of a zone, the
p.485number of occupants shall be the expected number specified by the building designer or the default occupancy density in Table 160.2-B times the occupiable floor area of the zone, whichever is greater. For spaces with fixed seating, the expected number of occupants shall be determined in accordance with the California Building Code Section 1004.6.
p.484naturally ventilated area shall extend to a distance not greater than five times the height of the ceiling along a line drawn between the outside edges of the two openings that are the farthest apart. Floor area outside that line shall comply with i as having openings on only one side of the zone. [ASHRAE 62.1:6.4.1.5]
p.485Ra = The area-based minimum ventilation airflow rate in Table 160.2-B.
Equation text: Az = The net occupiable floor area of the ventilation zone in square feet.
Needs visual review
p.484iv. Ceiling height. The ceiling height (H) to be used in Sections 160.2(c)2Ai through
p.484160.2(c)2Aiii shall be the minimum ceiling height in the space.p.485
p.485i. Use of transfer air is in accordance with Section 160.2(c)8; and
p.484SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.485SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY