1. Combustion air positive shut-off shall be provided on all newly installed boilers as follows:

p.517Section 160.4 – Mandatory Requirements for Water Heating Systems

p.517(a) Water-heating recirculation loops serving multiple dwelling units shall meet the requirements of

p.517Section 110.3(c)4.

p.517(b) Solar water-heating systems and collectors shall be certified and rated by the Solar Rating and

p.517Certification Corporation (SRCC), the International Association of Plumbing and Mechanical Officials, Research and Testing (IAPMO R&T), or a listing agency that is approved by the Executive Director.

p.517(c) Instantaneous water heaters with an input rating greater than 6.8 kBTU/hr (2kW) shall meet the

p.517requirements of Section 110.3(c)6.

p.517(d) Commercial boilers

p.5171. Combustion air positive shut-off shall be provided on all newly installed boilers as follows:

p.517A. All boilers with an input capacity of 2.5 MMBtu/h (2,500,000 Btu/h) and above, in which the

p.517boiler is designed to operate with a nonpositive vent static pressure.

p.517B. All boilers where one stack serves two or more boilers with a total combined input capacity

p.517per stack of 2.5 MMBtu/h (2,500,000 Btu/h).

p.5172. Boiler combustion air fans with motors 10 horsepower or larger shall meet one of the following for newly installed boilers:

p.517A. The fan motor shall be driven by a variable speed drive, or

p.517B. The fan motor shall include controls that limit the fan motor demand to no more than 30

p.517percent of the total design wattage at 50 percent of design air volume.

p.5173. Newly installed boilers with an input capacity 5 MMBtu/h (5,000,000 Btu/h) and greater shall maintain excess (stack-gas) oxygen concentrations at less than or equal to 5.0 percent by volume on a dry basis over firing rates of 20 percent to 100 percent. Combustion air volume shall be controlled with respect to firing rate or flue gas oxygen concentration. Use of a common gas and combustion air control linkage or jack shaft is prohibited.

p.517(e) Pipe Insulation

p.517All piping for multifamily domestic hot water systems shall be insulated and meet the applicable requirements 1 through 3 below:

p.5171. General Requirements.

p.517A. The first 8 feet of inlet cold water piping from the storage tanks, including piping between a

p.517storage tank and a heat trap shall be insulated.

p.517B. Insulation on the piping and domestic hot water system appurtenances shall be continuous.

p.517C. Pipe supports, hangers, and pipe clamps shall be attached on the outside of rigid pipe

p.517insulation to prevent thermal bridges.

p.517SECTION 160.4 – MANDATORY REQUIREMENTS FOR WATER HEATING SYSTEMS