p.5932025 Nonresidential Appendices 4. Unoccupied minimum airflow rate of each lab spaced, (cfm).
p.5935. Design inlet airflow rate o exhaust fan system, (cfm).
p.5936. Power of exhaust fan system at design conditions, (watts).
p.5937. Calculate wats/cfm at design conditions. Item (a)6 divided by item (a)5.
p.593(b) Listing of fume hoods design airflow rate by VAV (variable air volume) vs CV
p.593(constant volume) by space. When the total design airflow rate of fume hoods is greater than the unoccupied minimum airflow rate of the space, all fume hoods in the space shall be VAV.
p.593(c) Pressure independent flow control valves are used.
p.593(d) Document whether system has air filtration, scrubbers, or other air treatment
p.593devices.
p.593(e) Document fan power requirements described in (e)1 through (e)3 based on type of
p.593fan control used: none, simple turndown, wind responsive, contaminant monitoring.
p.5931. If control is “none,” and system has one of the filtration methods in item (d), water/cfm in item (a)7 shall be no greater than 0.85 watts/cfm of exhaust fan system airflow. Alternatively, the rated fan power does not surpass fan kWbudget as calculated per Section 140.4(c)1A.
p.5932. If control is “none,” and system does not have one of the filtration methods in item (d), watts/cfm in item (a)7 shall be no greater than 0.65 watts/cfm of exhaust fan system. Alternatively, the fan power does not surpass fan kWbudget as calculated per Section 140.4(c)1A.
p.5933. If control is “simple turndown,” “wind responsive,” or “contaminant monitoring,” exhaust fan system watts per cfm in item (a)7 shall be no greater than 1.3 watts per cfm of exhaust fan system airflow, and fan system shall comply with the applicable acceptance testing requirements in Nonresidential Reference Appendices NA 7.16.3 through NA 7.16.8.
p.593NA7.16.2 Functional Testing for VAV Lab Exhaust System with Occupancy Controls
p.593If control signals have been calibrated to measure flow rates and power consumption, recorded control signals are acceptable methods of measurement.
p.593Step 1: Simulate design conditions by opening all fume hood sashes and other exhaust
p.593devices such as snorkels to their design open position and occupy all lab spaces served by the exhaust fan system.
p.593(a) Verify that the occupant sensors can detect occupants in all portions of the spaces
p.593and are reporting occupied occupancy status to controller.
p.593(b) Verify that the inlet airflow rate of the exhaust fans meets the design flowrate.
p.593(c) Verify fan power under design conditions.
p.593(d) Measured power under design conditions shall be no greater than the design fan
p.593power.
p.593Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes