NA7.16.3 Construction Inspection for Simple Turndown Control

p.5942025 Nonresidential Appendices Step 2: Simulate minimum flowrate under occupied conditions by adjusting fume hoods and other exhaust devices. Adjust the thermostatic control so that the space temperature is within the dead band.

p.594(a) Verify that the occupant sensors can detect occupants in all portions of the spaces

p.594and are reporting occupied occupancy status to controller.

p.594(b) Verify that the total exhaust airflow rate of each space meets the minimum allowed

p.594occupied airflow rate.

p.594(c) Verify fan power under design conditions.

p.594(d) Measured power under minimum flowrate occupied conditions [Step 2(c)] shall be

p.594no greater than measured power under design conditions [Step 1(c)].

p.594Step 3: Simulate minimum flowrate under unoccupied conditions by adjusting fume hoods and other exhaust devices and vacate all lab spaces served by the exhaust fan system for at least 20 minutes so occupant control treats lab spaces as unoccupied. Adjust the thermostatic control so that the space temperature is within the dead band.

p.594(a) Verify that the occupant sensors are reporting unoccupied occupancy status to

p.594controller.

p.594(b) Verify that the total exhaust airflow rate of each space meets the minimum allowed

p.594unoccupied flowrate.

p.594(c) Verify fan power under minimum flowrate occupied conditions.

p.594(d) Measured power under minimum flowrate unoccupied conditions [Step 3(c)] shall

p.594be no greater than measured power under minimum flowrate occupied conditions [Step 2(c)].

p.594NA7.16.3 Construction Inspection for Simple Turndown Control

p.594Requirements for simple turndown control are required in addition to requirements for VAV lab exhaust system with occupancy controls in NA7.16.1 and NA7.16.2 if the builder uses simple turndown controls to meet fan system power consumption requirements.

p.594(a) Confirm that design values on plans and specifications and measured values are

p.594within 10%:

p.5941. Design inlet airflow rate of exhaust fan system (cfm).

p.5942. Power of exhaust fan system at design conditions (watts).

p.5943. Inlet airflow rate of exhaust fan system at occupied minimum acceptable airflow rate (cfm).

p.5944. Power of exhaust fan system at occupied minimum acceptable airflow rate (watts).

p.5945. Power of exhaust fan system at 60% of design exhaust fan system airflow rate (watts).

p.5946. Calculate watts/cfm at maximum design conditions, Item (a)2 divided by item (a)1.

p.594Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes