NA7.16.4 Functional Testing for Simple Turndown Control

p.5952025 Nonresidential Appendices (b) Measured occupied minimum acceptable exhaust fan system inlet airflow rate

p.595[item (a)3] is no greater than 60% of measured design exhaust fan system airflow rate [item(a)1].

p.595(c) Measured exhaust fan system power at 60% of design fan system airflow rate

p.595[item (a)5] is no greater than 40% of measured exhaust fan system power at design exhaust fan system airflow rate [item (a)2].

p.595NA7.16.4 Functional Testing for Simple Turndown Control

p.595If control signals have been calibrated to measured flow rates and power consumption, recorded control signals are acceptable methods of measurement.

p.595Step 1: Simulate design conditions. Adjust the thermostatic control so that the space temperature is within the dead band.

p.595(a) Verify that the occupant sensors can detect occupants in all portions of the spaces

p.595and are reporting occupied occupancy status to controller.

p.595(b) Verify that the exhaust fan system inlet airflow rate (cfm) meets the design airflow

p.595rate.

p.595(c) Record fan system power (watts).

p.595Step 2: Simulate turndown airflow rate. Adjust the thermostatic control so that the space

p.595temperature is within the dead band.

p.595(a) Record exhaust fan system inlet airflow rate (cfm).

p.595(b) Confirm that the airflow rate entering fan system for turndown airflow rate [Step

p.5952(b)] is no greater than 60% of the exhaust fan system design airflow rate [Step 1(b)].

p.595Step 3: Simulate 60% of design airflow rate. Adjust thermostatic control so that the space

p.595temperature is within the dead band.

p.595(a) Record fan system power (watts).

p.595(b) Confirm that the fan system power under 60% design airflow rate [Step 3(a)] is no

p.595greater than 40% of the exhaust fan system design airflow rate [Step 1(c)].

p.595NA7.16.5 Construction Inspection for Wind Speed/Direction Responsive Control

p.595Requirements for wind speed/direction responsive control are required in addition to requirements for VAV lab exhaust system with occupancy controls in NA7.16.1 and NA7.16.2 if the builder uses wind speed/direction responsive controls to meet fan system power consumption requirements.

p.595Verify and document the following prior to functional testing:

p.595(a) Wind speed and direction sensor is factory-calibrated (with calibration certificate)

p.595or field calibrated, as specified by Section 140.9(c)3C.

p.595Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes