p.5962025 Nonresidential Appendices (b) The sensor is located in a location and at a height that is outside the wake region
p.596of nearby structures and experiences similar wind conditions to the free stream environment above the exhaust stacks as specified by Section 140.9(c)3C.
p.596(c) The sensor is installed in close proximity to the fan that it will control so that it
p.596captures a representative wind speed/direction reading.
p.596(d) The sensor is wired correctly to the controls to ensure proper control of volume
p.596flow rate.
p.596(e) Wind speed/direction look-up table has been established and matches dispersion
p.596analysis results.
p.596(f) Verify the methodology to measure volume flow rate:
p.5961. Airflow sensor.
p.5962. Static pressure as proxy.
p.5963. Fan speed to volume flow rate curve.
p.5964. Other.
p.596(g) Confirm that design values on plans and specifications and measured values are
p.596within 10%:
p.5961. Design inlet airflow rate of exhaust fan system (cfm).
p.5962. Power of exhaust fan system at design conditions (watts).
p.5963. Inlet airflow rate of exhaust fan system at occupied minimum acceptable airflow rate (cfm).
p.5964. Power of exhaust fan system at occupied minimum acceptable airflow rate (watts).
p.5965. Power of exhaust fan system at 60% of design exhaust fan system airflow rate (watts).
p.5966. Calculate watts/cfm at maximum design conditions, Item (g)2 divided by item (g)1.
p.596(h) Measured occupied minimum acceptable exhaust fan system inlet airflow rate
p.596[item (g)3] is no greater than 60% of measured design exhaust fan system airflow rate [item(g)1].
p.596(i) Measured exhaust fan system power at 60% of design fan system airflow rate
p.596[item (g)5] is no greater than 40% of measured exhaust fan system power at design exhaust fan system airflow rate [item (g)2].
p.596NA7.16.6 Functional Testing for Wind Speed/Direction Responsive Control
p.596Step 1: Simulate design conditions.
p.596(a) Record airflow rate at the stack (cfm).
p.596(b) Record airflow rate entering the exhaust fan system (cfm).
p.596Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes