NA7.16.7 Construction Inspection for Monitored Contaminant Control

p.5972025 Nonresidential Appendices (c) Record exhaust fan system power at maximum wind speed (watts).

p.597(d) Restore all curve points.

p.597Step 2: Simulate the minimum occupied airflow rate by inducing a wind speed or

p.597overriding curve points.

p.597(a) Record airflow rate at the stack (cfm).

p.597(b) Record airflow rate entering the exhaust fan system (cfm).

p.597(c) Confirm that the airflow rate entering fan system airflow rate at minimum occupied

p.597conditions [Step 2(b)] is no greater than 60% of the exhaust fan system design airflow rate [Step 1(b)].

p.597Step 3: Simulate the 60% of design airflow rate by inducing wind speed or overriding

p.597curve points.

p.597(a) Record exhaust fan system power at 60% design airflow rate (watts).

p.597(b) Confirm that the fan system power at 60% design airflow rate [Step 3(a)] is no

p.597greater than 40% of the exhaust fan system airflow rate at maximum wind speed [Step 1(c)].

p.597(c) Restore all curve points.

p.597NA7.16.7 Construction Inspection for Monitored Contaminant Control

p.597Requirements for monitored contaminant control are required in addition to requirements for VAV lab exhaust system with occupancy controls in NA7.16.1 and NA7.16.2 if the builder uses monitored contaminant controls to meet fan system power consumption requirements.

p.597Verify and document the following tests prior to functional testing:

p.597(a) Contaminant sensor is factory-calibrated (with calibration certificate) or field

p.597calibrated, as specified by Section 140.9(c)3D.

p.597(b) The sensor is located within each exhaust plenum as specified by Section

p.597140.9(c)3D.

p.597(c) The sensor is wired correctly to the controls to ensure proper control of volume

p.597flow rate.

p.597(d) Contaminant concentration threshold has been established and matches

p.597dispersion analysis results.

p.597(e) Verify the methodology to measure volume flow rate:

p.5971. Airflow sensor

p.5972. Static pressure as proxy

p.5973. Fan speed to volume flow rate curve

p.5974. Other

p.597(f) If multiple sensors are present, ensure fan is controlled based on the highest

p.597concentration reading.

p.597Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes