p.5982025 Nonresidential Appendices (g) Confirm that design values on plans and specifications and measured values are
p.598within 10%:
p.5981. Design inlet airflow rate of exhaust fan system (cfm).
p.5982. Power of exhaust fan system at design conditions (watts).
p.5983. Inlet airflow rate of exhaust fan system at occupied minimum acceptable airflow rate (cfm).
p.5984. Power of exhaust fan system at occupied minimum acceptable airflow rate (watts).
p.5985. Power of exhaust fan system at 60% of design exhaust fan system airflow rate (watts).
p.5986. Calculate watts/cfm at maximum design conditions, Item (g)2 divided by item (g)1.
p.598(h) Measured occupied minimum acceptable exhaust fan system inlet airflow rate
p.598[item (g)3] is no greater than 60% of measured design exhaust fan system airflow rate [item(g)1].
p.598(i) Measured exhaust fan system power at 60% of design fan system airflow rate
p.598[item (g)5] is no greater than 40% of measured exhaust fan system power at design exhaust fan system airflow rate [item (g)2].
p.598NA7.16.8 Functional Testing for Monitored Contaminant Control
p.598Step 1: Ensure no contaminant event is present. Simulate design conditions.
p.598(a) Verify that the volume flow rate at the stack is at or above the minimum non-event
p.598value.
p.598(b) Record airflow rate at the stack (cfm).
p.598(c) Record airflow rate entering the exhaust fan system (cfm).
p.598(d) Record exhaust fan system power at design conditions (watts).
p.598Step 2: Simulate a contaminant event.
p.598(a) Verify that the volume flow rate at the stack is at or above the minimum non-event
p.598value.
p.598Step 3: Simulate the minimum occupied airflow rate.
p.598(a) Record airflow rate at the stack (cfm).
p.598(b) Record airflow rate entering the exhaust fan system (cfm).
p.598(c) Confirm that the airflow rate entering fan system airflow rate at minimum occupied
p.598conditions [Step 3(b)] is no greater than 60% of the exhaust fan system design airflow rate [Step 1(c)].
p.598Step 4: Simulate the 60% of design airflow rate.
p.598(a) Record exhaust fan system power at 60% design airflow rate (watts).
p.598Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes