RA3.3.3.4.2 Fan Efficacy Calculation (Watt/cfm)

p.3682025 Residential Appendices RA3.3.3.4.2 Fan Efficacy Calculation (Watt/cfm)

p.368The measured value for fan Watt draw (Watt) shall be divided by the measured value for airflow rate (cfm) to determine the fan efficacy (Watt/cfm).

p.368RA3.3.3.4.3 Compliance Criteria

p.368In order to comply with either the fan efficacy requirement, or the system airflow requirement, the following criteria shall be met:

p.368(a) The system airflow (cfm/ton) shall meet or exceed the system airflow compliance criteria

p.368specified in the Standards or on the Certificate of Compliance as applicable.

p.368(b) The calculated value for fan efficacy (Watt/cfm) shall be equal to or less than the fan

p.368efficacy compliance criterion specified in the Standards or on the Certificate of Compliance as applicable.

p.368RA3.3.4 Verification of Central Fan Ventilation Cooling Systems (CFVCS)

p.368When field verification and diagnostic testing of a central fan ventilation cooling system is required for compliance credit for the performance standards set forth in Standards Section 150.1(b), the CFVCS shall be verified according to the procedures in this section. Central fan ventilation cooling is not applicable to multifamily buildings.

p.368RA3.3.4.1 CFVCS Airflow Rate Measurements.

p.368The CFVCS airflow shall be verified according to the applicable procedures specified in RA3.3.3.1, to measure and record the following system airflow rates:

p.368a. The system airflow at high fan speed as required for compliance with Standards Section

p.368150.0(m)13.

p.368b. The system airflow rate at the speed used for ventilation cooling as specified on the

p.368Certificate of Compliance for the CFVCS.

p.368RA3.3.4.2 CFVCS Air Handler Fan Watt Draw Measurements.

p.368The CFVCS airflow shall be verified according to the applicable procedures specified in RA3.3.3.2, to measure and record the following system airflow Watt draw values:

p.368a. The system Watt draw at high fan speed as required for compliance with Standards

p.368Section 150.0(m)13.

p.368b. The system Watt draw at the speed used for ventilation cooling as specified on the

p.368Certificate of Compliance for the CFVCS.

p.368RA3.3.4.3 Determination of CFVCS Fan Efficacy

p.368Demonstrating compliance with fan efficacy requirements requires simultaneous measurement of the system airflow rate using Section RA3.3.4.1 procedures and fan Watt draw using Section RA3.3.4.2 procedures. The results of the simultaneous airflow rate and fan Watt draw measurements shall be used for calculation of a value for the forced air system fan efficacy as follows:

p.368– Residential Field Verification and Diagnostic Test Protocols