RA3.3.3.2.3 Air Handler Watt Draw Measurement Using Digital Utility Revenue Meter

p.3672025 Residential Appendices air handler. Record the Kh factor on the revenue meter, count the number of full revolutions of the meter wheel over a period exceeding 90 seconds. Record the number of revolutions (Nrev) and time period (trev, seconds). Compute the air handler watt draw (Wfan) using the following formula:

p.367Equation RA3.3-3 Air Handler Fan Watt Draw

Equation on PDF page 367: Wfan = (Kh x Nrev x 3600) / trev

Equation text: Wfan = (Kh x Nrev x 3600) / trev

Needs visual review

p.367

p.367Return all circuit breakers to their original positions.

p.367RA3.3.3.2.3 Air Handler Watt Draw Measurement Using Digital Utility Revenue Meter

p.367The air handler watt draw measurement shall be performed using the following procedures: all registers shall be fully open, and the air filter shall be installed. Turn on the system fan at the maximum speed used in the installation (usually the cooling speed when air conditioning is present; usually the cooling speed with outdoor air introduction if ventilation is provided through the return duct system) and turn off every circuit breaker except the one exclusively serving the air handler. Read the Watt draw from the digital utility meter digital display. Return all circuit breakers to their original positions.

p.367RA3.3.3.3 Determination of Forced Air System Fan Efficacy

p.367Demonstrating compliance with fan efficacy requirements requires simultaneous measurement of the system airflow rate using Section RA3.3.3.1 procedures and fan Watt draw using Section RA3.3.3.2 procedures. The results of the simultaneous airflow rate and fan Watt draw measurements are used for calculation of a value for the forced air system fan efficacy as follows:

p.367(a) The measured value for fan Watt draw (Watt) shall be divided by the measured value for

p.367airflow rate (cfm) to determine the fan efficacy (Watt/cfm).

p.367RA3.3.3.4 Determining Compliance with Fan Efficacy or System Airflow Requirements

p.367Compliance with the requirements for improved airflow or for improved fan efficacy both require simultaneous measurement of airflow and fan Watts. The simultaneous measurements shall be used to calculate the following values used to determine compliance:

p.367RA3.3.3.4.1 Airflow Calculation (cfm/ton)

p.367For packaged systems, and for split systems with only one indoor unit, the measured value for airflow (cfm) shall be converted to cfm per ton by dividing the measured system airflow rate by the nominal tons of condensing unit cooling capacity.

p.367For indoor units of multiple-split systems, the measured value for airflow in cfm shall be converted into cfm per ton by dividing the measured indoor unit airflow rate by the nominal tons of indoor unit cooling coil capacity.