RA3.3.3.1.5.2 Installer Compliance

p.3662025 Residential Appendices perform applicable alterations work on the return duct system or return grille in order to improve the system airflow rate.

p.366When performing these remedial actions determines that there is a fault, a corrective action shall be performed if possible. In many cases, airflow can be improved by adding a return duct and filter grille or enlarging the existing return duct or filter grille. Alteration of the return duct system is an alternative that shall be considered if applicable to the existing system, and if other remedial actions do not improve the airflow. Alteration of the return duct system to bring the system airflow rate into compliance is expected to be attainable for systems with ducts in an attic space with sufficient clearances for accommodating improvements to the return duct system.

p.366RA3.3.3.1.5.2 Installer Compliance

p.366For each of the listed remedial actions, the HVAC installer shall certify that the remedial action was performed and indicate whether the action was completed successfully or was not completed successfully. When a remedial action was not completed successfully the installer shall indicate on the installation certificate the reason the action was not completed successfully.

p.366RA3.3.3.1.5.3 ECC-Rater Compliance

p.366The ECC-Rater shall review the information submitted on the installation certificate and perform follow-up communications with the HVAC installer or the homeowner. The system complies if the ECC-Rater determines the remedial actions have been performed, and the information reported on the installation certificate is valid.

p.366RA3.3.3.2 Air Handler Fan Watt Draw Measurement Procedures

p.366The diagnostic air handler watt draw shall be measured using one of the following methods:

p.366RA3.3.3.2.1 Air Handler Watt Draw Measurement Using Portable Watt Meter

p.366The air handler watt draw measurement shall be performed using the following procedures: all registers shall be fully open, and the air filter shall be installed. Turn on the system fan at the maximum speed used in the installation (usually the cooling speed when air conditioning is present; usually the cooling speed with outdoor air introduction if ventilation is provided through the return duct system) and measure the fan watt draw (Wfan).

p.366When required to measure fan watt draw in packaged and heat pump units, it is recommended to use portable true power clamp-on meters to provide flexibility for isolating the correct fan wires serving in packaged or heat pump units.

p.366RA3.3.3.2.2 Air Handler Watt Draw Measurement Using Utility Revenue Meter

p.366The air handler watt draw measurement shall be performed using the following procedures: all registers shall be fully open, and the air filter shall be installed. Turn on the system fan at the maximum speed used in the installation (usually the cooling speed when air conditioning is present; usually the cooling speed with outdoor air introduction if ventilation is provided through the return duct system) and turn off every circuit breaker except the one exclusively serving the

p.366– Residential Field Verification and Diagnostic Test Protocols