3. Fenestration.

p.549B. Demising walls shall meet the requirements of Section 160.1(b)7. Vertical windows in

p.549demising walls between conditioned and unconditioned spaces shall have an area-weighted average U-factor no greater than the applicable value in Table 170.2-A.

p.550iii. Shading. Where Table 170.2-A requires a maximum RSHGC, the requirements shall be

p.5493. Fenestration.

p.550met with an area-weighted average RSHGC excluding the effects of interior shading, no greater than the applicable value in Table 170.2-A.

p.549A. Vertical fenestration and glazed doors in exterior walls shall comply with Subsections i, ii

p.549and iii:

p.550For the purposes of this paragraph, the RSHGC of a vertical window is:

p.549i. Percent fenestration area shall be limited in accordance with the applicable

p.550a. The solar heat gain coefficient of the window; or

p.549requirements of a and b below:

p.550b. Relative solar heat gain coefficient is calculated using Equation 170.2-A, if the

p.551a. The higher rated labeled VT shall be used with automatic controls to modulate the

p.549a. A total fenestration area no greater than 20 percent of the conditioned floor area;

p.550window has an overhang that extends beyond each side of the window jamb by a distance equal to the overhang’s horizontal projection.

p.551amount of light transmitted into the space in multiple steps in response to daylight levels or solar intensity;

p.549and

p.549b. A total fenestration area no greater than 40 percent of the gross exterior wall area.

p.551b. Chromogenic glazing shall be considered separately from other glazing; and

p.551c. Area-weighted averaging with other glazing that is not chromogenic shall not be

p.550I. That are in the first story of exterior walls that form a display perimeter; and

p.551permitted.

p.550II. For which codes restrict the use of overhangs to shade the windows.

p.549ii. Fenestration properties. Installed fenestration products, including glazed doors, shall

p.549have an area-weighted average U-factor, Relative Solar Heat Gain Coefficient (RSHGC), and Visible Transmittance (VT) meeting the applicable fenestration values in Table 170.2-A and shall be determined in accordance with Sections 110.6(a)2 and 110.6(a)3.

p.550I. the lower-rated labeled RSHGC shall be used with automatic controls to modulate the amount of heat flow into the space in multiple steps in response to daylight levels or solar intensity; and

p.549Vertical fenestration in demising walls between conditioned and unconditioned spaces is only required to comply with the area-weighted average U-factor requirement in Table 170.2-A.

p.551VT ≥ 0.11/WWR (Equation 170.2-B) where:

p.550II. chromogenic glazing shall be considered separately from other glazing; and

p.551WWR = Window Wall Ratio, the ratio of (i) the total window area of the entire

p.550III. area-weighted averaging with other glazing that is not chromogenic shall not be permitted.

p.551building to (ii) the total gross exterior wall area of the entire building. If the WWR is greater than 0.40, then 0.40 shall be used as the value for WWR in Equation 170.2-B. VT = Visible Transmittance of framed window.

p.551B. Skylights shall:

p.550RSHGC = SHGC × [1 + a × (2.72-PF – 1) × (sin(b × Az) + c)] (Equation 170.2-A) WHERE:

p.549modulate the amount of solar gain and light transmitted into the space in multiple steps in response to daylight levels or solar intensity;

p.551i. Have an area no greater than 5 percent of the gross exterior roof area Skylight Roof

p.551Ratio (SRR); and

Componentabc
Overhang0.1500.0087275.67
Exterior Horizontal Slat0.1440.0087275.13

p.549b. Chromogenic glazing shall be considered separately from other fenestration; and

p.549c. Area-weighted averaging with other fenestration that is not chromatic shall not be

p.551ii. Have an area-weighted performance rating U-factor no greater than the applicable

p.549permitted and shall be determined in accordance with Section 110.6(a).

p.551value in Table 170.2-A.

p.550RSHGC = Relative Solar Heat Gain Coefficient. SHGC = Solar Heat Gain Coefficient of the vertical fenestration. Az = Azimuth of the vertical fenestration I degrees. PF = Projection factor as calculated by Equation 140.3-C.

p.551iii. Solar heat gain coefficient. Have an area-weighted performance rating solar heat gain

p.551coefficient no greater than the applicable value in Table 170.2-A.

p.550iv. Vertical fenestration shall have an area-weighted average Visible Transmittance (VT) no

p.550less than the applicable value in Table 170.2-A, or Equation 170.2-B, as applicable.p.551

p.549SECTION 170.2 – PRESCRIPTIVE APPROACH

p.550SECTION 170.2 – PRESCRIPTIVE APPROACH

p.551SECTION 170.2 – PRESCRIPTIVE APPROACH