2. All skylit daylit zones and primary sidelit daylit zones shall be shown on building plans.

p.557(b) Minimum daylighting requirement for large enclosed spaces. In Climate Zones 2 through 15,

p.557conditioned enclosed spaces and unconditioned enclosed spaces that are greater than 5,000 ft2 and that are directly under a roof with ceiling heights greater than 15 feet shall meet the following requirements:

p.5571. A combined total of at least 75 percent of the floor area, as determined in building floor plan (drawings) view, shall be within one or more of the following:

p.557A. Primary sidelight daylight zone in accordance with Section 160.5(b)4Dib, or

p.557B. The total floor area in the space within a horizontal distance of 0.7 times the average ceiling

p.557height from the edge of rough opening of skylights.

p.5572. All skylit daylit zones and primary sidelit daylit zones shall be shown on building plans.

p.5573. General lighting in daylit zones shall be controlled in accordance with Section 160.5(b)4D.

p.5574. The total skylight area is at least 3 percent of the total floor area in the space within a horizontal distance of 0.7 times the average ceiling height from the edge of rough opening of skylights; or the product of the total skylight area and the average skylight visible transmittance is no less than 1.5 percent of the total floor area in the space within a horizontal distance of 0.7 times the average ceiling height from the edge of rough opening of skylights.

p.5575. All skylights shall have a glazing material or diffuser that has a measured haze value greater than 90 percent, tested according to ASTM D1003 (notwithstanding its scope) or another test method approved by the Commission.

p.557which there are plans to have:

p.557A. A floor area of less than or equal to 5,000 square feet; or

p.557B. Ceiling heights of less than or equal to 15 feet. This exception shall not be used for S-1 or S-

p.5572 (storage), or for F-1 or F-2 (factory) occupancies.

p.557comply with minimum Appliance Efficiency Regulations as specified in Sections 110.0 through 110.2 and the applicable requirements of Subsections 1 through 4.

p.5571. Sizing and equipment selection—common use areas. Mechanical heating and mechanical cooling equipment serving common use areas of multifamily buildings shall be the smallest size, within the available options of the desired equipment line, necessary to meet the design heating and cooling loads of the building, as calculated according to Subsection 2 below.

p.557SECTION 170.2 – PRESCRIPTIVE APPROACH