2. Calculations—common use areas. In making equipment sizing calculations under Subsection (c)1, all of the following rules shall apply:

p.5582. Calculations—common use areas. In making equipment sizing calculations under Subsection (c)1, all of the following rules shall apply:

p.558A. Heating and cooling loads. Heating and cooling system design loads shall be determined in

p.558accordance with the method in the 2017 ASHRAE Handbook, Fundamentals Volume, or as specified in a method approved by the Commission.

p.558B. Indoor design conditions. Indoor design temperature and humidity conditions for comfort

p.558applications shall be determined using ASHRAE Standard 55 or the 2021 ASHRAE Handbook, Fundamentals Volume, except that winter humidification and summer dehumidification shall not be required.

p.558C. Outdoor design conditions. Outdoor design conditions shall be selected from Reference

p.558Joint Appendix JA2, which is based on data from the ASHRAE Climatic Data for Region X or the ASHRAE Handbook Fundamentals Volume. Heating design temperatures shall be no lower than the 99.0 percent Heating Dry Bulb or the Heating Winter Median of Extremes values. Cooling design temperatures shall be no greater than the 0.5 percent Cooling Dry Bulb and Mean Coincident Wet Bulb values.

p.558D. Ventilation. Outdoor air ventilation loads shall be calculated using the ventilation rates

p.558required in Section 160.2(c)3.

p.558E. Envelope. Envelope heating and cooling loads shall be calculated using envelope

p.558characteristics, including square footage, thermal conductance, solar heat gain coefficient or shading coefficient, and air leakage, consistent with the proposed design.

p.558F. Lighting. Lighting heating and cooling loads shall be based on actual design lighting levels or

p.558power densities as specified in Section 170.2(e)1.

p.558G. People. Occupant density shall be based on the expected occupancy of the building and

p.558shall be the same as determined under Section 160.2(c)3A, if used. Sensible and latent heat gains shall be as listed in the 2017 ASHRAE Handbook—Fundamentals, Chapter 18.

p.558H. Process loads. Loads caused by a process shall be based upon actual information on the

p.558intended use of the building.

p.558I. Miscellaneous equipment. Equipment loads other than process loads shall be calculated

p.558using design data compiled from one or more of the following sources:

p.558i. Actual information based on the intended use of the building; or

p.558ii. Published data from manufacturers’ technical publications or from technical societies,

p.558such as the ASHRAE Handbook, Applications Volume; or