p.4741. Insulation material alone without the facing shall have a water absorption rate no greater than 0.3 percent when tested in accordance with ASTM C272, Test Method A – 24-Hour-Immersion; and
p.473D. The requirements in Reference Residential Appendix RA4.5.1.
p.4731. In Climate Zones 1–16, the earth floor of unvented crawl space shall be covered with a Class I or Class II vapor retarder. This requirement shall also apply to controlled ventilation crawl space for buildings complying with the Exception to Section 160.1(c).
p.4742. Water vapor permeance no greater than 2.0 perm/inch when tested in accordance with ASTM C272; and
p.4743. Concrete slab perimeter insulation shall be protected from physical damage and ultraviolet light deterioration; and
p.4732. In Climate Zones 14 and 16, a Class I or Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior walls, vented attics and unvented attics with air-permeable insulation.
p.4744. Insulation for a heated slab floor shall meet the requirements of Section 110.8(g).
p.473(e) Fenestration products. Fenestration separating conditioned space from unconditioned space or
p.473outdoors shall meet the requirements of either Item 1 or 2 below:
p.4731. Fenestration, including skylight products, must have a maximum U-factor of 0.58.
p.4732. The area-weighted average U-factor of all fenestration, including skylight products, shall not exceed 0.58.
p.473(f) Installation of fireplaces, decorative gas appliances and gas logs. If a masonry or factory-built
p.473fireplace is installed, it shall comply with Section 110.5, Section 4.503 of Part 11, and shall have the following:
p.4731. Closable metal or glass doors covering the entire opening of the firebox; and
p.4732. A combustion air intake to draw air from the outside of the building, which is at least 6 square inches in area and is equipped with a readily accessible, operable and tight-fitting damper or combustion-air control device; and
p.4733. A flue damper with a readily accessible control.
p.473(g) Slab edge Insulation. Slab edge insulation shall meet the following minimum specifications:p.474
p.473SECTION 160.1 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES
p.474SECTION 160.1 – MANDATORY REQUIREMENTS FOR BUILDING ENVELOPES