p.343(r) DDC controller logic using ASHRAE Guideline 36. HVAC systems with DDC controllers shall
p.344SWHCAP = design capacity of all service water heating (SWH) systems, excluding
p.343use controller logic originating from a programming library based on sequences of operation from ASHRAE Guideline 36 in accordance with the following:
p.344systems expected to operate less than 5 hours per week, such as instant-hot water systems for emergency eyewash stations.
p.338(n) Mechanical system shut-off. Any directly conditioned space with operable wall or roof
p.339equipment fans, circulation pumps and terminal unit fans when there is no call for heating or cooling in the zone.
p.342TABLE 140.4-K – ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW (≥ 8,000
p.338openings to the outdoors shall be provided with interlock controls that disable or reset the temperature setpoint to 55°F for mechanical heating and disable or reset the temperature setpoint to 90°F for mechanical cooling to that space when any such opening is open for more than 5 minutes.
p.341TABLE 140.4-J – ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW (< 8,000
p.342HOURS / YEAR)
p.341HOURS / YEAR)
p.3431. Requirement applies to all controllers that are capable of being programmed in the field; and
p.344HCAP = design capacity of all space-heating systems.
| % Outdoor Air at Full Design Airflow | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ≥ 10% and < 20% | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| ≥ 20% and < 30% | ≥ 15,000 | ≥ 20,000 | NR | NR | NR | NR | NR | NR | NR | NR | ≥ 18,500 | ≥ 18,500 | ≥ 18,500 | ≥ 18,500 | ≥ 18,500 | ≥ 18,500 |
| ≥ 30% and < 40% | ≥ 13,000 | ≥ 15,000 | NR | NR | NR | NR | NR | NR | NR | NR | ≥ 15,000 | ≥ 15,000 | ≥ 15,000 | ≥ 15,000 | ≥ 15,000 | ≥ 15,000 |
| ≥ 40% and < 50% | ≥ 10,000 | ≥ 12,000 | NR | NR | NR | NR | NR | NR | NR | ≥ 22,000 | ≥ 10,000 | ≥ 10,000 | ≥ 10,000 | ≥ 10,000 | ≥ 10,000 | ≥ 10,000 |
| ≥ 50% and < 60% | ≥ 9,000 | ≥ 10,000 | NR | ≥ 18,500 | NR | NR | NR | NR | NR | ≥ 17,000 | ≥ 8,000 | ≥ 8,000 | ≥ 8,000 | ≥ 8,000 | ≥ 8,000 | ≥ 8,000 |
| ≥ 60% and < 70% | ≥ 7,000 | ≥ 7,500 | NR | ≥ 16,500 | NR | NR | NR | NR | ≥ 20,000 | ≥ 15,000 | ≥ 7,000 | ≥ 7,000 | ≥ 7,000 | ≥ 7,000 | ≥ 7,000 | ≥ 7,000 |
| ≥ 70% and < 80% | ≥ 6,500 | ≥ 7,000 | NR | ≥ 15,000 | NR | NR | NR | NR | ≥ 17,000 | ≥ 14,000 | ≥ 5,000 | ≥ 5,000 | ≥ 5,000 | ≥ 5,000 | ≥ 5,000 | ≥ 5,000 |
| ≥ 80% | ≥ 4,500 | ≥ 6,500 | NR | ≥ 14,000 | NR | NR | NR | NR | ≥ 15,000 | ≥ 13,000 | ≥ 2,000 | ≥ 2,000 | ≥ 2,000 | ≥ 2,000 | ≥ 2,000 | ≥ 2,000 |
| % Outdoor Air at Full Design Airflow | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
| ≥10% and <20% | ≥10,000 | ≥10,000 | NR | NR | NR | NR | NR | NR | NR | ≥40,000 | ≥40,000 | ≥20,000 | ≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 |
| ≥20% and <30% | ≥2,000 | ≥5,000 | ≥13,000 | ≥9,000 | ≥9,000 | NR | NR | NR | NR | ≥15,000 | ≥15,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 |
| ≥30% and <40% | ≥2,000 | ≥3,000 | ≥10,000 | ≥6,500 | ≥6,500 | NR | NR | NR | ≥15,000 | ≥7,500 | ≥7,500 | ≥3,000 | ≥3,000 | ≥3,000 | ≥3,000 | ≥3,000 |
| ≥40% and <50% | ≥2,000 | ≥2,000 | ≥8,000 | ≥6,000 | ≥6,000 | NR | NR | NR | ≥12,000 | ≥6,000 | ≥6,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥50% and <60% | ≥2,000 | ≥2,000 | ≥7,000 | ≥6,000 | ≥6,000 | NR | NR | ≥20,000 | ≥10,000 | ≥5,000 | ≥5,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥60% and <70% | ≥2,000 | ≥2,000 | ≥6,000 | ≥6,000 | ≥6,000 | NR | NR | ≥18,000 | ≥9,000 | ≥4,000 | ≥4,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥70% and <80% | ≥2,000 | ≥2,000 | ≥6,000 | ≥5,000 | ≥5,000 | NR | NR | ≥15,000 | ≥8,000 | ≥3,000 | ≥3,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥80% | ≥2,000 | ≥2,000 | ≥6,000 | ≥5,000 | ≥5,000 | NR | NR | ≥12,000 | ≥7,000 | ≥3,000 | ≥3,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
p.344B. The heat recovery system shall include a heat recovery chiller, or other means,
p.3432. Requirement applies to the entirety or all applicable portions of equipment control for configurations included in the programming library; and
p.344capable of transferring the lesser of the following from spaces in cooling to spaces in heating and/or to the SWH system:
p.3401. used for another energy recovery system,
p.3402. not allowed by the California Mechanical Code (Title 24, Part 4) (CMC) for use in energy recovery systems with leakage potential, or
p.3433. The programming library shall be certified to the Energy Commission as meeting the requirements of Reference Joint Appendix JA18.
p.344i. 25 percent of the peak heat rejection of the cooling system.
p.3403. of Class 4 as specified in Section 120.1(g).
p.344ii. 25 percent of (SWHCAP + HCAP).
p.337(l) Reserved.
p.338(o) Exhaust system transfer air. Conditioned supply air delivered to any space with mechanical
p.338exhaust shall not exceed the greater of:
p.337(m) Fan control. Each cooling system listed in Table 140.4-I shall be designed to vary the indoor
p.342NOTES to table 140.4-K:
p.341NOTES to Table 140.4-J:
p.3393. DOAS supply and exhaust fans shall have a minimum of three speeds to facilitate system balancing.
p.337fan airflow as a function of load and shall comply with the following requirements:
p.3381. The supply flow required to meet the space heating or cooling load; or
p.3421. Flow rates in Table 140.4-K represent the design supply fan airflow rate in CFM.
p.3411. Flow rates in Table 140.4-J represent the design supply fan airflow rate in CFM.
p.3422. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.p.343
p.3371. DX and chilled water cooling systems that control the capacity of the mechanical cooling directly based on occupied space temperature shall:
p.3382. The ventilation rate required by the authority having jurisdiction, the facility Environmental Health and Safety Department, or by Section 120.1(c)3; or
p.3412. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.p.342
p.3394. DOAS with mechanical cooling providing ventilation to multiple zones and operating in conjunction with zone heating and cooling systems shall not use heating or heat recovery to warm supply air above 60°F when representative building loads or outdoor air temperature indicates that the majority of zones require cooling.
p.3442. Heat recovery for service water heating.
p.337A. Have a minimum of two stages of fan control with no more than 66 percent speed when operating on stage 1; and
p.3383. The mechanical exhaust flow minus the available transfer air. Available transfer air shall be from another conditioned space or return air plenums on the same floor and same smoke or fire compartment, and that at their closest point are within 15 feet of each other.
p.344If the building is required to have simultaneous mechanical heat recovery by Section 140.4(s)1, and SWHCAP ≥ 500 kBtuh, then the heat recovery system shall also heat or preheat the service hot water. The heat recovery system shall have the capacity to transfer the smaller of:
p.337B. Draw no more than 40 percent of the fan power at full fan speed, when operating at
p.339(q) Exhaust air heat recovery. Fan systems designed to operate to the criteria listed in Table
p.33766 percent speed.
p.339140.4-J, Table 140.4-K, or where required by Section 140.4(a)3, shall include an exhaust air heat recovery system that meets the following:
p.343(s) Mechanical heat recovery
p.3372. All other systems, including but not limited to DX cooling systems and chilled water systems that control the space temperature by modulating the airflow to the space, shall have proportional fan control such that at 50 percent air flow the power draw is no more than 30 percent of the fan power at full fan speed.
p.3431. Simultaneous mechanical heat recovery.
p.3391. A sensible energy recovery ratio of at least 60 percent or an enthalpy recovery ratio of at least 50 percent for both heating and cooling design conditions and a rating in accordance with AHRI 1060.
p.344A. 30 percent of the peak heat rejection of the cooling system; or
p.343A. Simultaneous mechanical heat recovery is required for newly constructed buildings
p.344B. 30 percent of SWHCAP.
p.343that meet either i or ii:
p.3373. Systems that include an air side economizer to meet Section 140.4(e)1 shall have a minimum of two speeds of fan control during economizer operation.
p.343i. CHL + 0.1 x CLL ≥ 200 tons and SWHCAP + HCAP ≥ 2200 kBtuh; or
p.343ii. CCAP ≥ 300 tons and SWHCAP + 0.1 x HCAP ≥ 700 kBtuh
p.3392. Energy recovery bypass or control to disable energy recovery and to directly economize with ventilation air based on outdoor air temperature limits specified in Table 140.4-G. For energy recovery systems where the transfer of energy cannot be stopped, bypass shall prevent the total airflow rate of either outdoor air or exhaust air through the energy recovery exchanger from exceeding 10 percent of the full design airflow rate.
p.338(p) Dedicated outdoor air systems (DOAS). HVAC systems that utilize a dedicated outdoor air
p.338system (DOAS) such as a DX-DOAS, HRV or ERV unit to condition, temper, or filter 100 percent outdoor air separate from local or central space-conditioning systems serving the same space shall meet the following criteria:
p.341SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.342SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.343CCAP = design capacity of all mechanical cooling systems.
p.343CHL = coincident peak cooling load of all spaces with a design equipment power
p.343density > 5 watts/ft2 and a minimum outdoor airflow requirement < 0.5 cfm/ft2 (i.e., high load spaces).
p.3381. DOAS unit fan systems with input power less than 1 kW shall not exceed a total combined fan power of 1.0 W/cfm. DOAS with fan power greater than or equal to 1 kW shall meet the requirements of Section 140.4 (c).
| Cooling System Type | Fan Motor Size | Cooling Capacity |
|---|---|---|
| DX Cooling | Any | ≥ 65,000 Btu/hr |
| Chilled Water and Evaporative | ≥ 1/4 HP | Any |
p.343CLL = CCAP - CHL. If the design includes capacity for future cooling systems, then
p.343assume 20 percent of future systems serve high load spaces.p.344
p.3382. The DOAS supply air shall be delivered directly to the occupied space or at the outlet of any terminal heating or cooling coils and shall cycle off any zone heating and coolingp.339
p.337SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.338SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.339SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.340SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.343SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS
p.344SECTION 140.4 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS