3. Dwelling unit space-conditioning systems. (part 2 of 3)

Scanned crop of table from PDF page 582
AIR DENSITY CORRECTION FACTORS p.571 Download CSV
Altitude (ft)Correction factor
<3,0001.000
≥3,000 and <4,0000.896
≥4,000 and <5,0000.864
≥5,000 and <6,0000.832
≥6,0000.801
ECONOMIZER TRADE-OFF TABLE FOR COOLING SYSTEMS p.574 Download CSV
Climate ZoneEfficiency Improvement a
170%
265%
365%
465%
570%
630%
730%
830%
930%
1030%
1130%
1230%
1330%
1430%
1530%
1670%
AIR ECONOMIZER HIGH LIMIT SHUT OFF CONTROL REQUIREMENTS p.575 Download CSV
Device TypeaClimate ZonesRequired High Limit (Economizer Off When): EquationbRequired High Limit (Economizer Off When): Description
Fixed Dry Bulb1, 3, 5, 11-16TOA > 75°FOutdoor air temperature exceeds 75°F
Fixed Dry Bulb2, 4, 10TOA > 73°FOutdoor air temperature exceeds 73°F
Fixed Dry Bulb6, 8, 9TOA > 71°FOutdoor air temperature exceeds 71°F
Fixed Dry Bulb7TOA > 69°FOutdoor air temperature exceeds 69°F
Differential Dry Bulb1, 3, 5, 11-16TOA > TRA°FOutdoor air temperature exceeds return air temperature
Differential Dry Bulb2, 4, 10TOA > TRA-2°FOutdoor air temperature exceeds return air temperature minus 2°F
Differential Dry Bulb6, 8, 9TOA > TRA-4°FOutdoor air temperature exceeds return air temperature minus 4°F
Differential Dry Bulb7TOA > TRA-6°FOutdoor air temperature exceeds return air temperature minus 6°F
Fixed Enthalpyc + Fixed DrybulbAllhOA > 28 Btu/lbc or TOA > 75°FOutdoor air enthalpy exceeds 28 Btu/lb of dry airc or Outdoor air temperature exceeds 75°F
MINIMUM EFFICIENCY FOR PROPELLER OR AXIAL FAN OPEN-CIRCUIT COOLING TOWERS (GPM/hp) p.579 Download CSV
CZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
42.1706070708080808080607080608042.1
TABLE 170.2-E-1: Default values for Fan kWdesign Based on Motor Nameplate HP1,2 p.571 Download CSV
Motor Nameplate HPDefault Fan kWdesign with variable speed drive (Fan kWdesign)Default Fan kWdesign without variable speed drive (Fan kWdesign)
<10.960.89
≥1 and <1.51.381.29
DIRECT EXPANSION (DX) UNIT REQUIREMENTS FOR COOLING STAGES AND COMPRESSOR DISPLACEMENT p.576 Download CSV
Cooling CapacityMinimum Number of Mechanical Cooling StagesMinimum Compressor Displacement
≥ 65,000 Btu/h and < 240,000 Btu/h3 stages≤ 35% full load
≥ 240,000 Btu/h4 stages≤ 25% full load
CHILLED WATER SYSTEM COOLING CAPACITYTotal Building Chilled Water System Capacity, Minus Capacity of the Cooling units with Air Economizers p.573 Download CSV
Climate ZonesBuilding Water-Cooled Chilled Water SystemAir-Cooled Chilled Water Systems or District Chilled Water Systems
15≥ 960,000 Btu/h (280 kW)≥ 1,250,000 Btu/h (365 kW)
1-14≥720,000 Btu/h (210 kW)≥940,000 Btu/h (275 kW)
16≥1,320,000 Btu/h (385 kW)≥1,720,000 Bu/h (505 kW)