AIR ECONOMIZER HIGH LIMIT SHUT OFF CONTROL REQUIREMENTS p.575Download CSV
Device Typea
Climate Zones
Required High Limit (Economizer Off When): Equationb
Required High Limit (Economizer Off When): Description
Fixed Dry Bulb
1, 3, 5, 11-16
TOA > 75°F
Outdoor air temperature exceeds 75°F
Fixed Dry Bulb
2, 4, 10
TOA > 73°F
Outdoor air temperature exceeds 73°F
Fixed Dry Bulb
6, 8, 9
TOA > 71°F
Outdoor air temperature exceeds 71°F
Fixed Dry Bulb
7
TOA > 69°F
Outdoor air temperature exceeds 69°F
Differential Dry Bulb
1, 3, 5, 11-16
TOA > TRA°F
Outdoor air temperature exceeds return air temperature
Differential Dry Bulb
2, 4, 10
TOA > TRA-2°F
Outdoor air temperature exceeds return air temperature minus 2°F
Differential Dry Bulb
6, 8, 9
TOA > TRA-4°F
Outdoor air temperature exceeds return air temperature minus 4°F
Differential Dry Bulb
7
TOA > TRA-6°F
Outdoor air temperature exceeds return air temperature minus 6°F
Fixed Enthalpyc + Fixed Drybulb
All
hOA > 28 Btu/lbc or TOA > 75°F
Outdoor air enthalpy exceeds 28 Btu/lb of dry airc or Outdoor air temperature exceeds 75°F
MINIMUM EFFICIENCY FOR PROPELLER OR AXIAL FAN OPEN-CIRCUIT COOLING TOWERS (GPM/hp) p.579Download CSV
CZ 1
CZ 2
CZ 3
CZ 4
CZ 5
CZ 6
CZ 7
CZ 8
CZ 9
CZ 10
CZ 11
CZ 12
CZ 13
CZ 14
CZ 15
CZ 16
42.1
70
60
70
70
80
80
80
80
80
60
70
80
60
80
42.1
TABLE 170.2-E-1: Default values for Fan kWdesign Based on Motor Nameplate HP1,2 p.571Download CSV
Motor Nameplate HP
Default Fan kWdesign with variable speed drive (Fan kWdesign)
Default Fan kWdesign without variable speed drive (Fan kWdesign)
<1
0.96
0.89
≥1 and <1.5
1.38
1.29
DIRECT EXPANSION (DX) UNIT REQUIREMENTS FOR COOLING STAGES AND COMPRESSOR DISPLACEMENT p.576Download CSV
Cooling Capacity
Minimum Number of Mechanical Cooling Stages
Minimum Compressor Displacement
≥ 65,000 Btu/h and < 240,000 Btu/h
3 stages
≤ 35% full load
≥ 240,000 Btu/h
4 stages
≤ 25% full load
CHILLED WATER SYSTEM COOLING CAPACITYTotal Building Chilled Water System Capacity, Minus Capacity of the Cooling units with Air Economizers p.573Download CSV
Climate Zones
Building Water-Cooled Chilled Water System
Air-Cooled Chilled Water Systems or District Chilled Water Systems