3. Dwelling unit space-conditioning systems. (part 3 of 3)

p.584TABLE 170.2-I: ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW (<8,000 HOURS / YEAR)

ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW (<8,000 HOURS / YEAR) p.584 Download CSV
% Outdoor Air at Full Design AirflowCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
≥10% and <20%NRNRNRNRNRNRNRNRNRNRNRNRNRNRNRNR
≥20% and <30%≥15,000≥20,000NRNRNRNRNRNRNRNR≥18,500≥18,500≥18,500≥18,500≥18,500≥18,500
≥30% and <40%≥13,000≥15,000NRNRNRNRNRNRNRNR≥15,000≥15,000≥15,000≥15,000≥15,000≥15,000
≥40% and <50%≥10,000≥12,000NRNRNRNRNRNRNR≥22,000≥10,000≥10,000≥10,000≥10,000≥10,000≥10,000
≥50% and <60%≥9,000≥10,000NR≥18,500NRNRNRNRNR≥17,000≥8,000≥8,000≥8,000≥8,000≥8,000≥8,000
≥60% and <70%≥7,000≥7,500NR≥16,500NRNRNRNR≥20,000≥15,000≥7,000≥7,000≥7,000≥7,000≥7,000≥7,000
≥70% and <80%≥6,500≥7,000NR≥15,000NRNRNRNR≥17,000≥14,000≥5,000≥5,000≥5,000≥5,000≥5,000≥5,000
≥80%≥4,500≥6,500NR≥14,000NRNRNRNR≥15,000≥13,000≥2,000≥2,000≥2,000≥2,000≥2,000≥2,000

p.584FOOTNOTES TO TABLE 170.2-I:

p.5841. Flow rates in Table 140.4-G represent the design supply fan airflow rate in CFM. 2. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.

p.583i. used for another energy recovery system;

p.584TABLE 170.2-J: ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW (≥8,000 HOURS / YEAR)

p.583ii. not allowed by the California Mechanical Code (Title 24, Part 4) for use in energy

ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW (≥8,000 HOURS / YEAR) p.584 Download CSV
% Outdoor Air at Full Design AirflowCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8CZ 9CZ 10CZ 11CZ 12CZ 13CZ 14CZ 15CZ 16
≥10% and <20%≥10,000≥10,000NRNRNRNRNRNRNR≥40,000≥40,000≥20,000≥10,000≥10,000≥10,000≥10,000
≥20% and <30%≥2,000≥5,000≥13,000≥9,000≥9,000NRNRNRNR≥15,000≥15,000≥5,000≥5,000≥5,000≥5,000≥5,000
≥30% and <40%≥2,000≥3,000≥10,000≥6,500≥6,500NRNRNR≥15,000≥7,500≥7,500≥3,000≥3,000≥3,000≥3,000≥3,000
≥40% and <50%≥2,000≥2,000≥8,000≥6,000≥6,000NRNRNR≥12,000≥6,000≥6,000≥2,000≥2,000≥2,000≥2,000≥2,000
≥50% and <60%≥2,000≥2,000≥7,000≥6,000≥6,000NRNR≥20,000≥10,000≥5,000≥5,000≥2,000≥2,000≥2,000≥2,000≥2,000
≥60% and <70%≥2,000≥2,000≥6,000≥6,000≥6,000NRNR≥18,000≥9,000≥4,000≥4,000≥2,000≥2,000≥2,000≥2,000≥2,000
≥70% and <80%≥2,000≥2,000≥6,000≥5,000≥5,000NRNR≥15,000≥8,000≥3,000≥3,000≥2,000≥2,000≥2,000≥2,000≥2,000
≥80%≥2,000≥2,000≥6,000≥5,000≥5,000NRNR≥12,000≥7,000≥3,000≥3,000≥2,000≥2,000≥2,000≥2,000≥2,000

p.583recovery systems with leakage potential; or

p.583iii. of Class 4 as specified in Section 160.2(c)8.

p.584Footnotes to TABLE 170.2-J:

p.5841. Flow rates in Table 140.4-G represent the design supply fan airflow rate in CFM. 2. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.

p.584SECTION 170.2 – PRESCRIPTIVE APPROACH

p.583SECTION 170.2 – PRESCRIPTIVE APPROACH