p.585(d) Domestic Hot Water Systems Water-heating systems shall meet the applicable requirements of 1
p.586B. For gas or propane systems serving multiple dwelling units, the water-heating system that
p.586includes the following components shall be installed:
p.585or 2 below:
| Component | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Unitary4 – Balanced Ventilation System1 HRV/ERV Sensible Recovery Efficiency | 0.67 | 0.67 | NR | 0.67 | NR | NR | NR | NR | NR | NR | 0.67 | 0.67 | 0.67 | 0.67 | NR | 0.67 |
| Unitary4 – Balanced Ventilation System1 HRV/ERV Fan Efficacy (W/cfm) | 0.6 | 0.6 | 1.0 | 0.6 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 0.6 | 0.6 | 0.6 | 0.6 | 1.0 | 0.6 |
| Unitary4 – Balanced Ventilation System1 Non-HRV/ERV Fan Efficacy (W/cfm) | NR | NR | NR | NR | 0.4 | 0.4 | 0.4 | 0.4 | 0.4 | 0.4 | NR | NR | NR | NR | 0.4 | NR |
| Unitary4 – Heat Pump3, HSPF22 | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN |
| Unitary4 – Dual-Fuel Heat Pump3, AFUE | MIN | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | MIN |
| Unitary4 – Refrigerant Charge Verification or Fault Indicator Display | NR | REQ | NR | NR | NR | NR | NR | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | NR |
| Unitary4 – SEER2 | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN |
| Central5 - Balanced Ventilation Systems1 Sensible Recovery Efficiency or Effectiveness | 0.67 | 0.67 | NR | 0.67 | NR | NR | NR | NR | NR | NR | 0.67 | 0.67 | 0.67 | 0.67 | NR | 0.67 |
| Central5 - Balanced Ventilation Systems1 Bypass Function | REQ | REQ | NR | REQ | NR | NR | NR | NR | NR | NR | REQ | REQ | REQ | REQ | NR | REQ |
| Central5 – Central Fan Integrated Ventilation System Fan Efficacy | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ |
| Duct Insulation in Unconditioned Space | R 8 | R 8 | R 6 | R 8 | R 6 | R 6 | R 6 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 | R 8 |
| Water Heating - All Buildings System Shall meet Section 170.2(d) | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ |
p.586i. For Climate Zones 1 through 9, gas service water-heating systems with a total installed gas
p.5851. Individual Systems. For systems serving individual dwelling units, the water-heating system shall meet the requirement of either A, or B, or shall meet the performance compliance requirements of Section 170.1. For recirculation distribution systems serving individual dwelling units, only demand recirculation systems with manual on/off control as specified in the Reference Appendix RA4.4.9 shall be used.
p.586water-heating input capacity of 1 MMBtu/h or greater shall have gas service water-heating equipment with a minimum thermal efficiency of 90 percent. Multiple units are allowed to meet this requirement with an input capacity-weighted average of at least 90 percent.
p.585A. A single 240 volt heat pump water heater. In addition, meet the following:
p.585i. A compact hot water distribution system as specified in Reference Appendix RA4.4.6 in
p.585climate zones 1 and 16; and
p.585ii. A drain water heat recovery system that is field verified as specified in the Reference
p.586ii. A solar water-heating system meeting the installation criteria specified in Reference
p.585Appendix RA3.6.9 in Climate Zone 16.
p.586Residential Appendix RA4 and with a minimum solar savings fraction of either a. or b. below:
p.585B. A single heat pump water heater that meets the requirements of NEEA Advanced Water
p.585Heater Specification Tier 3 or higher. In addition, for climate zone 16, a drain water heat recovery system that is field verified as specified in Reference Appendix RA3.6.9.
p.586a. A minimum solar savings fraction of 0.20 in Climate Zones 1 through 9 or a minimum
p.586solar savings fraction of 0.35 in Climate Zones 10 through 16; or
p.586b. A minimum solar savings fraction of 0.15 in Climate Zones 1 through 9 or a minimum
p.586solar savings fraction of 0.30 in Climate Zones 10 through 16. In addition, a drain water heat recovery system that is field verified as specified in the Reference Appendix RA3.6.9.
p.586C. All hot water piping shall be sized in accordance with the California Plumbing Code Appendix M.
p.586D. The central system shall have a recirculation system with a mechanical or digital thermostatic
p.5852. Central Systems. For systems serving multiple dwelling units, the water-heating system shall meet the applicable requirement of A through F, or shall meet the performance compliance requirements of Section 170.1:
p.587Footnotes to TABLE 170.2-K:
p.586master mixing valve on each distribution supply and return loop, and meet the requirements specified in the Residential Reference Appendix RA4.4.19.
p.5871. Requirements only apply when using Balanced Ventilation to meet 160.2(b)2Aivb. 2. HSPF2 means "heating seasonal performance factor." 3. A supplemental heating unit may be installed in a space served directly or indirectly by a primary heating system, provided that the unit thermal capacity does not exceed 2 kilowatts or 7,000 Btu/hr and is controlled by a time-limiting device not exceeding 30 minutes. 4. Unitary system serving one dwelling unit 5. Central system serving multiple dwelling units
p.585A. For heat pump water-heating systems serving multiple dwelling units, the water-heating
p.585system shall be installed according to the manufacturer’s design and installation guidelines and meet the following requirements, or meet the requirements of NEEA Advanced Water Heater Specification for commercial heat pump water heater Tier 2 or higher:
p.586E. Insulation for hot water pipes and plumbing appurtenances shall be field verified as specified in
p.586Residential Reference Appendix RA3.6.3.
p.586F. A water-heating system serving multiple dwelling units determined by the Executive Director to
p.585i. The primary heat pump water heater shall be a single-pass heat pump water heater.
p.586use no more energy than the one specified in Subsection A or B above.p.587
p.585ii. The hot water return from the recirculation loop shall connect to a recirculation loop
p.587SECTION 170.2 – PRESCRIPTIVE APPROACH
p.585tank and shall not directly connect to the primary heat pump water heater inlet or the primary thermal storage tanks.
p.585iii. The fuel source for the recirculation loop tank shall be electricity.
p.585iv. The primary storage tank temperature setpoint shall be at least 135°F.
p.585v. The recirculation loop tank temperature setpoint shall be at least 10°F lower than the
p.585primary thermal storage tank temperature setpoint.
p.585vi. The minimum heat pump water heater compressor cut-off temperature shall be equal
p.585to or lower than 40°F ambient air temperature. vii. Design documentation shall be provided in accordance with JA14.4.p.586