p.531A. Where the existing luminaire does not meet the luminaire BUG requirements in Section
p.531160.5(c)1; and
p.531B. Spacing between existing poles is greater than six times the mounting height of the existing
p.531luminaires; and
p.531C. Where no additional poles are being added to the site; and
p.531D. Where new wiring to the luminaires is not being installed; and
p.531E. Provided that the connected lighting power wattage is not increased.
p.5312. Controls for outdoor lighting. Outdoor lighting shall be independently controlled from other electrical loads, and the controls for outdoor lighting shall meet the following functional requirements:
p.531A. Daylight availability. All installed outdoor lighting shall be controlled by a photo control,
p.531astronomical time-switch control or other control capable of automatically shutting OFF the outdoor lighting when daylight is available.
p.531B. Automatic scheduling controls.
p.531i. Automatic scheduling controls shall be installed for all outdoor lighting. Automatic
p.531scheduling controls may be installed in combination with motion sensing controls or other outdoor lighting controls.
p.531ii. Automatic scheduling controls shall be capable of reducing the outdoor lighting power
p.531by 50 to 90 percent, and separately capable of turning the lighting OFF, during scheduled unoccupied periods.
p.531iii. Automatic scheduling controls shall allow scheduling of a minimum of two nighttime
p.531periods with independent lighting levels, and may include an override function that turns lighting ON during its scheduled dim or OFF state for no more than two hours when an override is initiated.
p.531SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES