SECTION 150.0 – MANDATORY FEATURES AND DEVICES (part 2 of 3)

Scanned crop of table from PDF page 415
Text in this table

SECTION 150.0 – MANDATORY FEATURES AND DEVICES B. For single-family dwellings and townhouses at the rough-in stage of construction prior to installation of the dwelling’s interior finishing: i. Air-handling unit installed. If the air-handling unit is installed and the ducts are connected directly to the air handler, the total leakage of the duct system shall not exceed 5 percent of the air handler airflow as determined utilizing the procedures in Reference Residential Appendix Sections RA3.1.4.3.2, RA3.1.4.3.2.1 and RA3.1.4.3.3. ii. Air-handling unit not yet installed. If the air-handling unit is not yet installed, the total leakage of the duct system shall not exceed 4 percent of the air handler airflow as determined utilizing the procedures in Reference Residential Appendix Sections RA3.1.4.3.2, RA3.1.4.3.2.2 and RA3.1.4.3.3. 12. Air filtration. A. System types specified in Subsections i, ii, and iii shall be provided with air filters in accordance with Sections 150.0(m)12B, 150.0(m)12C, and 150.0(m)12D. System types specified in Subsection i shall also comply with Section 150.0(m)12E. i. Mechanical space-conditioning systems that supply air to an occupiable space through ductwork exceeding 10 feet (3 m) in length. ii. Mechanical supply-only ventilation systems and makeup air systems that provide outside air to an occupiable space. iii. The supply side of mechanical balanced ventilation systems, including heat recovery ventilation systems, and energy recovery ventilation systems that provide outside air to an occupiable space. Exception 1 to Section 150.0(m)12A: Evaporative coolers are not required to comply with the air filtration requirements in Section 150.0(m)12. B. System design and installation. i. The system shall be designed to ensure that all recirculated air and all outdoor air supplied to the occupiable space is filtered before passing through any system’s thermal conditioning components. Exception 1 to Section 150.0(m)12Bi: For heat recovery ventilators and energy recovery ventilators the location of the filters required by Section 150.0(m)12 may be downstream of a system thermal conditioning component, provided the system is equipped with ancillary filtration upstream of the system’s thermal conditioning component. ii. All systems shall be designed to accommodate the clean-filter pressure drop imposed by the system air filter(s). The design airflow rate and maximum allowable clean-filter pressure drop at the design airflow rate applicable to each air filter shall be determined and reported on labels according to Subsection iv below. Systems specified in Section 150.0(m)12Ai shall be equipped with air filters that meet either Subsection a or b below.

Equation on PDF page 421: Afloor = dwelling-unit floor area, ft2

Equation text: Afloor = dwelling-unit floor area, ft2

Needs visual review

p.421
Equation 150.0-D.: wsf = weather and shielding factor from Table 150.0-D.

Equation text: wsf = weather and shielding factor from Table 150.0-D.

Needs visual review

Equation 150.0-D. — p.422
Equation on PDF page 421: Nbr = number of bedrooms (not to be less than 1)

Equation text: Nbr = number of bedrooms (not to be less than 1)

Needs visual review

p.421
Equation on PDF page 422: Hr = reference height, 8.2 ft (2.5 m).

Equation text: Hr = reference height, 8.2 ft (2.5 m).

Needs visual review

p.422
Equation on PDF page 416: Aface = air filter face area, the product of air filter nominal length x nominal width, ft2.

Equation text: Aface = air filter face area, the product of air filter nominal length x nominal width, ft2.

Needs visual review

p.416
Equation on PDF page 416: Qfilter = design airflow rate for the air filter, ft3/min.

Equation text: Qfilter = design airflow rate for the air filter, ft3/min.

Needs visual review

p.416
Equation on PDF page 422: Qfan = Qtot – F (Qinf × Aext) (Equation 150.0-F)

Equation text: Qfan = Qtot – F (Qinf × Aext) (Equation 150.0-F)

Needs visual review

p.422
Equation on PDF page 421: Q50 = Vdu x 2 ACH50/60 min

Equation text: Q50 = Vdu x 2 ACH50/60 min

Needs visual review

p.421
Equation on PDF page 416: Vface = air filter face velocity ≤ 150, ft/min.

Equation text: Vface = air filter face velocity ≤ 150, ft/min.

Needs visual review

p.416
Equation on PDF page 422: Qfan = required mechanical ventilation rate, cfm (L/s).

Equation text: Qfan = required mechanical ventilation rate, cfm (L/s).

Needs visual review

p.422
Equation on PDF page 421: Q50 = leakage rate at 50 Pa.

Equation text: Q50 = leakage rate at 50 Pa.

Needs visual review

p.421
Equation on PDF page 422: Qtot = total required ventilation rate, cfm (L/s) from

Equation text: Qtot = total required ventilation rate, cfm (L/s) from

Needs visual review

p.422
Equation on PDF page 421: Vdu = dwelling unit conditioned volume, ft3.

Equation text: Vdu = dwelling unit conditioned volume, ft3.

Needs visual review

p.421
Equation on PDF page 421: ACH50 = air changes per hour at 50 Pa (0.2 inch water).

Equation text: ACH50 = air changes per hour at 50 Pa (0.2 inch water).

Needs visual review

p.421
Equation 150.0-B.: Qinf = effective annual average infiltration rate, cfm (L/s) from Equation 150.0-E.

Equation text: Qinf = effective annual average infiltration rate, cfm (L/s) from Equation 150.0-E.

Needs visual review

Equation 150.0-B. — p.422
Equation on PDF page 421: Q50 = Vdu x Verified ACH50/60 min (Equation 150.0-D)

Equation text: Q50 = Vdu x Verified ACH50/60 min (Equation 150.0-D)

Needs visual review

p.421
Equation on PDF page 421: Q50 = leakage rate at 50 Pa.

Equation text: Q50 = leakage rate at 50 Pa.

Needs visual review

p.421
Equation on PDF page 421: Vdu = dwelling unit conditioned volume, ft3.

Equation text: Vdu = dwelling unit conditioned volume, ft3.

Needs visual review

p.421
Equation on PDF page 421: ACH50 = air changes per hour at 50 Pa (0.2 inch water).

Equation text: ACH50 = air changes per hour at 50 Pa (0.2 inch water).

Needs visual review

p.421
Equation on PDF page 421: Qinf = 0.052 × Q50 × wsf × [H/Hr]z (Equation 150.0-E)

Equation text: Qinf = 0.052 × Q50 × wsf × [H/Hr]z (Equation 150.0-E)

Needs visual review

p.421
Equation on PDF page 420: Qtot = 0.03Afloor + 7.5(Nbr + 1) (Equation 150.0-B)

Equation text: Qtot = 0.03Afloor + 7.5(Nbr + 1) (Equation 150.0-B)

Needs visual review

p.420
Equation on PDF page 420: Qtot = total required ventilation rate, cfm

Equation text: Qtot = total required ventilation rate, cfm

Needs visual review

p.420